Main Menu user defined parameters.
There are 8 numeric and 8 Boolean user-defined parameters available in the Main Menu. All
of them are Read Only type locally for the Room Panel (Read & Write type for the higher level
system) and they are written to EEPROM memory (register values are remembered after the
room Panel restart or power failure).
Each parameter has to be activated to be visible. Active parameters are displayed in the
main menu in a specified sequence (read more in section
Refreshing time
)
After Room Panel restart user-defined parameters are not displayed until they are
overwritten from a higher level system (Master Controller).
The Main Menu user-defined parameters are implemented for displaying additional
information.
11
Submenus with user defined parameters
The Room Panel is equipped with a special group of registers which allows to define
parameters by the user.
User defined parameters are grouped into 6 submenus.
1.
Temperature submenu
2.
Fan submenu
3.
Light submenu
4.
Blind submenu
5.
Alarm submenu
6.
Occupancy submenu
Each submenu is automatically activated if one of the parameters assigned to that submenu
is active. When the particular submenu is active, then the icon of that submenu is displayed
in the Main Menu (see
Submenu Icon Display table
). Fan and Occupancy submenu icons are
displayed in different configuration according to actual Fan and Occupancy Status (see
sections about
Fan registers
and
Occupancy registers
).
In each submenu there are available 8 numeric and 8 Boolean user-defined parameters.
All user-defined parameters in each submenu are used for displaying and setting different
values locally from the Room Panel. All are written to EEPROM memory (register values are
remembered after the Room Panel restart or power failure).
Access to each submenu can be protected by a password (see
Submenu protection
).
11.1
Numeric parameter type registers
Each submenu has 8 numeric user-defined parameters. Each of user-defined parameters
has the same structure: contains 7 registers dedicated to different functionalities and
purposes. Each register isdescribed below (Exact Modbus address for each register: see the
list of all Modbus registers
).