iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 64 / 121
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
that time. Default time: 500ms.
40222
221
0xDD
SUBMENU_ICON_FLASHING_TIME Read & Write
Memory
Time which is the base for calculating frequency of
Icon flashing. Icons are visible for 100% of the time
value stored in the register and hidden for 20% of
that time. Default time 1000ms.
40223
222
0xDE
ENTER_MENU_TIME
Read & Write
Memory
By default 2 sec.
40224
223
0xDF
EXIT_EDIT_TIME
Read & Write
Memory
By default 5 sec.
40225
224
0xE0
EXIT_MENU_TIME
Read & Write
Memory
By default 10 sec.
40226
225
0xE1
CO2_SETPOINT_FOR_ALARM
Read & Write
Memory
CO2 Alarm setpoint. By default 1500 ppm.
40227
226
0xE2
CO2_HYSTERESIS_FOR_ALARM
Read & Write
Memory
CO2 Alarm hysteresis. By default 100 ppm.
30230
229
0xE5
ALARM_STATUS
Read Only
CO2 Current alarm Status
30301
300
0x12C
TEMPERATURE_SENSOR
Read Only
Actual temperature sensor value with offset.
30302
301
0x12D
HUMIDITY_SENSOR
Read Only
Actual humidity sensor value with offset.
30303
302
0x12E
CO2_SENSOR
Read Only
Actual CO2 sensor value with offset.
40304
303
0x12F
TEMPERATURE_SENSOR_OFFSET Read & Write
Memory
Temperature sensor offset. Default is 0.
40305
304
0x130
HUMIDITY_SENSOR_OFFSET
Read & Write
Memory
Humidity sensor offset. Default is 0.
40306
305
0x131
CO2_SENSOR_OFFSET
Read & Write
Memory
CO2 sensor offset. Default is 0.
40307
306
0x132
TEMPERATURE_FILTER
Read & Write
Memory
By default 60 sec
40308
307
0x133
HUMIDITY_FILTER
Read & Write
Memory
By default 60 sec
40309
308
0x134
CO2_FILTER
Read & Write
Memory
By default 60 sec
40310
309
0x135
TEMPERATURE_NAME
(32
–
bits)
Read & Write
Memory
Displayed temperature sensor name. : TEMP
40312
311
0x137
HUMIDITY_NAME
(32
–
bits)
Read & Write
Memory
Displayed humidity sensor name. : HUMI
40314
313
0x139
CO2_NAME
(32
–
bits)
Read & Write
Memory
Displayed CO2 sensor name. : CO2