iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 114 / 121
12.1.8
Occupancy Submenu
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
40099
98
0x62
SETTINGSNUMERIC1
PRESENT_VALUE
Read &
Write
Memory
Present value of the parameter
41266
1265
0x4F1
SETTINGS_MENU_ACTIVE_POINTS
Read &
Write
Memory
Number of active parameters in submenu
41269
1268
0x4F4
SETTINGSNUMERIC1
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40812
1270
0x4F6
SETTINGSNUMERIC1
STEP
Read &
Write
Memory
STEP during parameter value changing.
The default value is 0
41272
1271
0x4F7
SETTINGSNUMERIC1
LOW_LIMIT
Read &
Write
Memory
Minimal value of the parameter.
The default value is 0
41273
1272
0x4F8
SETTINGSNUMERIC1
HIGH_LIMIT
Read &
Write
Memory
Maximal value of the parameter.
The default value is 0
41274
1273
0x4F9
SETTINGSNUMERIC1
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of displaying
in Submenu
41275
1274
0x4FA
SETTINGSNUMERIC1
CONFIGURATION
Read &
Write
Memory
Bit
Name
0
1
0 Active
Not active(def) Active(def)
2
FirstPointActive Not
decimal(def)
Decimal(def)
3
SecondPointActive Not
decimal(def)
Decimal(def)
4
ThirdPointActive Not
decimal(def)
Decimal(def)
6
C unit active
not_visible(def) visible
7
F unit active
not_visible(def) visible
8
Pa unit active
not_visible(def) visible
9
Lx unit active
not_visible(def) visible
10 ppm unit active
not_visible(def) visible
11 m3/h unit active not_visible(def) visible
12 %Rh unit active
not_visible(def) visible
13 l/s unit active
not_visible(def) visible
14 % unit active
not_visible(def) visible
15 h unit active
not_visible(def) visible