iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 45 / 121
8
Occupancy Registers
Occupancy mode setting is available from Main Menu level. When Room Panel is in Active
Mode, single pushing of the OK button leads the user to Occupancy Edit Submenu. On 14-
segment display block text “OCCM” flashes (with frequency calculated on
SUBMENU_ICON_FLASHING_TIME basis) and on 8-segment display block name of current
OCCUPANCY_MODE is displayed.(see
Occupancy Mode Name
).
8.1
OCCUPANCY
_
CURRENT
_
STATUS (41701)
The register contains numeric value corresponding to actual occupancy status. Particular
register value is the base for displaying determined group of icons (see table below). This
register has software limitation where the maximum value is 3. The register value can be
used as an actual occupancy status indication.
Register
value
Icon
0
1
2
3
Human symbol
blinks
Table 22 Occupancy Current Status
8.2
OCCUPANCY
_
MODE (41702)
The register contains numeric value corresponding to OCCUPANCY_MODE. There are two
different occupancy modes which can be selected locally from the Occupancy Edit Submenu
level. (see table below). To enter Occupancy Edit Submenu, the OK button needs to be
pushed when the Room Panel is in Active Mode. This register has software limitation where
the maximum value is 1. Default texts for particular occupancy modes can be changed (see
Occupancy Mode Name
).
Occupancy Mode
text on LDC
Register value
UNOC
0
OCC
1
Table 23 Occupancy Current Status