iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 70 / 121
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
Memory
40343
342
0x156
MAIN_MENU_NUMERIC5
CONFIGURATION
Read &
Write
Memory
See
the
table
in
MAIN_MENU_NUMERIC1Configuration(30323)
40056
55
0x37
MAIN_MENU_NUMERIC6
PRESENTVALUE
Read &
Write
Memory
Present value of the parameter
40345
344
0x158
MAIN_MENU_NUMERIC6
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40347
346
0x15A
MAIN_MENU_NUMERIC6
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Main Menu
40348
347
0x15B
MAIN_MENU_NUMERIC6
CONFIGURATION
Read &
Write
Memory
See
the
table
in
MAIN_MENU_NUMERIC1Configuration(30323)
40350
349
0x15D
MAIN_MENU_NUMERIC7
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40057
56
0x38
MAIN_MENU_NUMERIC7
PRESENTVALUE
Read &
Write
Memory
Present value of the parameter
40352
351
0x15E
MAIN_MENU_NUMERIC7
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Main Menu
40353
352
0x15F
MAIN_MENU_NUMERIC7
CONFIGURATION
Read &
Write
Memory
See
the
table
in
MAIN_MENU_NUMERIC1Configuration(30323)
40058
57
0x39
MAIN_MENU_NUMERIC8
PRESENTVALUE
Read &
Write
Memory
Present value of the parameter
40355
354
0x162
MAIN_MENU_NUMERIC8
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40357
356
0x164
MAIN_MENU_NUMERIC8
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Main Menu
40358
357
0x165
MAIN_MENU_NUMERIC8
CONFIGURATION
Read &
Write
Memory
See
the
table
in
MAIN_MENU_NUMERIC1Configuration(30323)
40107
106
0x6A
MAIN_MENU_BOOLEAN
ALLPRESENTVALUES
Read &
Write
Memory
Bit
Name
0
1
0 Boolean1PresentValue Not active(def) Active
1 Boolean2PresentValue Not active(def) Active
…
…
…
…
6 Boolean7PresentValue Not active(def) Active