iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 24 / 121
4.8.1.3 LCD_ICON_FLASHING_TIME (40221)
It is possible to set Icon blinking frequency. Register LCD_ICON_FLASHING_TIME stores the
time which constitutes the base for calculating Icon blinking frequency. This register has
min. value of 50 ms. Default value is 500 ms (the icons are visible fo 500 ms and hidden for
500/4=125 ms).
4.8.1.4 SUBMENU_ICON_FLASHING (40229)
Each bit of the register switches on blinking of particular Icons.
Setting true value for a particular bit causes blinking of a single Icon which is assigned to
that bit according to Table no. 13 below.
Table 13 Submenu Icon Display
Bit
Icon Name
Icon
0
Temperature
1
Fan 1
2
Fan 2
3
Fan 3
4
Fan 4
5
Fan 5
6
Fan 6
7
Light
8
Blind
9
Alarms
10
Occupancy 1
11
Occupancy 2
12
Occupancy 3