iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 98 / 121
12.1.6
Blind Submenu
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
40083
82
0x52
BLINDNUMERIC1
PRESENT_VALUE
Read &
Write
Memory
Present value of the parameter
40960
959
0x3BF
BLIND_MENU
ACTIVE_POINTS
Read &
Write
Memory
Number of active parameters in submenu
40963
962
0x3C2
BLINDNUMERIC1
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40965
964
0x3C4
BLINDNUMERIC1
STEP
Read &
Write
Memory
STEP during parameter value changing.
The default value is 0
40966
965
0x3C5
BLINDNUMERIC1
LOW_LIMIT
Read &
Write
Memory
Minimal value of the parameter.
The default value is 0
40967
966
0x3C6
BLINDNUMERIC1
HIGH_LIMIT
Read &
Write
Memory
Maximal value of the parameter.
The default value is 0
40968
967
0x3C7
BLINDNUMERIC1
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Submenu
40969
968
0x3C8
BLINDNUMERIC1
CONFIGURATION
Read &
Write
Memory
Bit
Name
0
1
0 Active
Not active(def) Active(def)
2
FirstPointActive Not
decimal(def)
Decimal(def)
3
SecondPointActive Not
decimal(def)
Decimal(def)
4
ThirdPointActive Not
decimal(def)
Decimal(def)
6
C unit active
not_visible(def) visible
7
F unit active
not_visible(def) visible
8
Pa unit active
not_visible(def) visible
9
Lx unit active
not_visible(def) visible
10 ppm unit active
not_visible(def) visible
11 m3/h unit active not_visible(def) visible
12 %Rh unit active
not_visible(def) visible
13 l/s unit active
not_visible(def) visible
14 % unit active
not_visible(def) visible
15 h unit active
not_visible(def) visible
40084
83
0x53
BLINDNUMERIC2
Read &
Present value of the parameter