11.1.1
XPresentValue (X = [1.8])
The register contains actual value of the parameter. The default value is 0.
11.1.2
XName (X = [1.8])
There is one 32-bit register which can contain up to 4 characters (ASCII code) which can be
displayed as a text (name) on 14-segment display block together with the Present Value
register (displayed on 8-segment display block). In case when particular character value is 0
(NULL), the character is not displayed. Lower case characters are automatically changed
into upper case characters. The default name is NUMX where X=[1.8] (ex. Register value for
name
“
NUM1
”
= 1295076949).
11.1.3
XPriority (X = [1.8])
The register contains value which determines parameter priority. The parameter priority
determines the sequence of parameters displayed inside the particular submenu. The
parameter with the highest priority is displayed as a first parameter in submenu. The
parameter with the lowest priority is displayed as a last parameter in Submenu. If two or
more parameters have the same priority, the sequence of displaying based on register
addresses (the register with the lowest address is displayed as first). Default priority for all
user-defined parameters is 0.
11.1.4
XSTEP (X = [1.8])
The register contains value which is a STEP during parameter value edition. The default
value is 0.
11.1.5
XLowLimit (X = [1.8])
The register contains minimal value of the parameter (minimal value which can be set locally
from the Room Panel). The default value is 0.
11.1.6
XHIGH_LIMIT (X = [1.8])
The register contains maximal value of the parameter (maximal value which can be set
locally from the Room Panel). The default value is 0.
11.1.7
XConfiguration (X = [1.8])
11.1.7.1
Visibility bit 0
Bit 0 activates parameter visibility. If bit 0 is active, parameter actual value is displayed in the
particular Submenu with the defined display priority. By default bit is 0 (Parameter is
inactive).