HD2 IP55 High-ingress Protection Series
Communication protocol
-283-
Function
Address
Data description
R/W
Communication-based
value setting
2001H Communication-based frequency setting (0–
Fmax, unit: 0.01 Hz)
R/W
2002H PID
setting,
range
(0–1000,
1000
corresponding to 100.0%)
In the actual operation, set P00.01 to 2 and P00.06 to 8.
The command transmitted by the master is as follows:
01 10
20 00 00 0204
00 01 03 E8 3B 10
inverter Continuous Parameter
Parameter
Number of
Froward
10 Hz
CRC
address
write
address
quantity
bytes
running
command
If the operation is successful, the following response is returned:
01 10 20 00 00 02
4A 08
inverter
address
Continuous
write
command
Parameter
address
Parameter
quantity
CRC
Example 2: Set "Acceleration time" of the inverter whose address is 01H to 10s, and
"Deceleration time" to 20s.
Function
code
Name
Description
Default value Modify
P00.11
Acceleration
time 1
Setting range of P00.11 and P00.12: 0.0–
3600.0s
Depend on
model
○
P00.12
Deceleration
time 1
Depend on
model
○
The address of P00.11 is 000B, 10s is 0064H in the hexadecimal form, and 20s is 00C8H in
the hexadecimal form.
The command transmitted by the master is as follows:
01 10
00 0B 00 0204
00 64 00 C8 F2 55
invert
er
address
Continuous
write
command
Parameter
address
Parameter
quantity
Number of
bytes
10s
20s
CRC
If the operation is successful, the following response is returned:
01 10 00 0B 00 02
30 0A
inverter
address
Continuous
write
command
Parameter
address
Parameter
quantity
CRC
Summary of Contents for HD2 IP Series
Page 1: ......
Page 16: ......
Page 40: ......
Page 107: ......
Page 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Page 213: ......
Page 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Page 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Page 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Page 361: ......