HD2 IP55 High-ingress Protection Series Inverter
-92-
Set
value
Function
Description
27
Z pulse output
Output is valid when the encoder Z pulse is arrived,
and is invalid after 10 ms.
28
During pulse superposition Output is valid when the pulse superposition terminal
input function is valid
29
STO action
Output when STO fault occurred
30
Positioning completed Output is valid when position control positioning is
completed
31
Spindle zeroing completed Output is valid when spindle zeroing is completed
32
Spindle scale-division
completed
Output is valid when spindle scale-division is
completed
33
In speed limit
Output is valid when the frequency is limited
34
Virtual terminal output of
EtherCAT/PROFINET
communication
The corresponding signal is output according to the set
value of PROFINET communication. When it is set to
1, the ON signal is output, and when it is set to 0, the
OFF signal is output.
35
Reserved
36
Speed/position control
switch-over completed
Output is valid when the mode switch-over is
completed
37–40
Reserved
41
C_Y1
C_Y1 from PLC (set P27.00 to 1)
42
C_Y2
C_Y2 from PLC (set P27.00 to 1)
43
C_HDO
C_HDO from PLC (set P27.00 to 1)
44
C_RO1
C_RO1 from PLC (set P27.00 to 1)
45
C_RO2
C_RO2 from PLC (set P27.00 to 1)
46
C_RO3
C_RO3 from PLC (set P27.00 to 1)
47
C_RO4
C_RO4 from PLC (set P27.00 to 1)
48–63
Reserved
/
Related parameter list:
Function
code
Name
Description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse output
1: Open collector output
0
P06.01
Y1 output selection 0: Invalid
1: In running
2: In forward running
3: In reverse running
4: In jogging
5: inverter fault
6: Frequency level detection FDT1
7: Frequency level detection FDT2
8: Frequency reached
9: Running in zero speed
10: Reach upper limit frequency
11: Reach lower limit frequency
0
P06.02
HDO output selection
0
P06.03
Relay RO1 output
selection
1
P06.04
Relay RO2 output
selection
5
Summary of Contents for HD2 IP Series
Page 1: ......
Page 16: ......
Page 40: ......
Page 107: ......
Page 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Page 213: ......
Page 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Page 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Page 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Page 361: ......