HD2 IP55 High-ingress Protection Series Inverter
-220
running frequency logic
P33.01=2
,
Hibernation according to
deviation
P33.02
Hibernation
start
frequency
P00.05~P00.04
Running frequency≤P33.02, and
continues P33.04 time, then enter
hibernation.
25.00H
z
○
P33.03
Hibernation
start
deviation
0.0~30.0% (Corresponds to PID max
value)
PID1 polarity is positive, feedback >
reference, and deviation > P33.03,
continues P33.04 time, then enter
hibernation.
PID1 polarity is negative, feedback <
reference, and deviation > P33.03,
continues P33.04 time, then enter
hibernation.
5.0%
○
P33.04
Enter
hibernation
delay time
0.0~3600.0s
60.0s
○
P33.05
PID1
reference
boost value
-100.0~100.0% (Corresponds to PID
reference)
Before hibernation is enabled and before
entering to hibernation, add PID1
reference boost (P33.05) on the basis of
PID1 reference as the final PID1
reference value
10.0%
○
P33.06
Max. boost
time
0.000~60.000s
Used to avoid the case when the running
frequency reaches the upper limit while
the feedback cannot reach the set value
after boost, inverter runs continuously.
inverter will enter hibernation
immediately after P33.06 boost time.
10.000
s
○
P33.07
Hibernation
wakes up
frequency
P00.05~P00.03
When wake up, PID output value add
P33.07 setting frequency directly.
The wake-up logic is as followings:
20.00H
z
○
Summary of Contents for HD2 IP Series
Page 1: ......
Page 16: ......
Page 40: ......
Page 107: ......
Page 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Page 213: ......
Page 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Page 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Page 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Page 361: ......