HD2 IP55 High-ingress Protection Series
Function parameter list
-175-
Function
code
Name
Description
Default
value Modify
2: inverter output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0: The inverter continues running after
overload/underload alarm.
1: The inverter continues running after
underload alarm, and stops running after
overload fault.
2: The inverter continues running after overload
alarm, and stops running after underload fault.
3:
The
inverter stops
running
after
overload/underload fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: inverter overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
P11.09
Overload
pre-alarm
detection
level
If the inverter or motor output current is larger
than the overload pre-alarm detection level
(P11.09), and the duration exceeds the overload
pre-alarm detection time (P11.10), overload pre-
alarm signal will be outputted.
Output current
Overload pre-alarm
threshold
Time t
Pre-alarm time t
Pre-alarm time t
Y,
RO1, RO2
Time t
Setting range of P11.09: P11.11–200% (relative
value determined by the ones place of P11.08)
Setting range of P11.10: 0.1–3600.0s
G model:
150%
P model:
120%
○
P11.10
Overload
pre-alarm
detection time
1.0s
○
P11.11
Underload
pre-alarm
detection
level
Underload pre-alarm signal will be outputted if
the output current of the inverter or motor is lower
than underload pre-alarm detection level
), and the duration exceeds underload
pre-alarm detection time (
Setting range of
: 0– P11.09 (relative
value determined by the ones place of P11.08)
Setting range of
: 0.1–3600.0s
50%
○
P11.12
Underload
pre-alarm
detection time
1.0s
○
Summary of Contents for HD2 IP Series
Page 1: ......
Page 16: ......
Page 40: ......
Page 107: ......
Page 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Page 213: ......
Page 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Page 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Page 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Page 361: ......