HD2 IP55 High-ingress Protection Series
Function parameter list
-185-
Function
code
Name
Description
Default
value Modify
3: Do not alarm and stop as per the stop mode
(under all control modes)
P14.06
Communication
processing
action
0x00–0x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is
invalid
1: Communication password protection is
valid
0x00
○
P14.07–
P14.24
Reserved
/
/
/
P15 group––Functions of communication extension card 1
Function
code
Name
Description
Default
value Modify
P15.00–
P15.27 See the operation manual of communication extension card for details
P15.28
Master/slave CAN
communication
address
0–127
1
◎
P15.29
Master/slave CAN
communication
baud rate
selection
0: 50Kbps
1: 100 Kbps
2: 125Kbps
3: 250Kbps
4: 500Kbps
5: 1M bps
4
◎
P15.30
Master/slave CAN
communication
timeout period
0.0 (invalid)–300.0s
0.0s
○
P15.31–
P15.69 See the operation manual of communication extension card for details
P16 group––Functions of communication
extension card 2
Function
code
Name
Description
Default
value Modify
P16.00–
P16.23 See the operation manual of communication extension card for details
P16.24
Identification time
for the extension
card in card slot 1
0.0–600.0s
If it is set to 0.0, identification fault will not be
detected
0.0s
○
P16.25
Identification time
for the extension
card in card slot 2
0.0–600.0s
If it is set to 0.0, offline fault will not be
detected
0.0s
○
Summary of Contents for HD2 IP Series
Page 1: ......
Page 16: ......
Page 40: ......
Page 107: ......
Page 176: ...HD2 IP55 High ingress Protection Series Inverter 162 Function parameter list...
Page 213: ......
Page 271: ...HD2 IP55 High ingress Protection Series Troubleshooting 251 7 6 8 Overcurrent...
Page 294: ...HD2 IP55 High ingress Protection Series Inverter 274...
Page 360: ...HD2 IP55 High ingress Protection Series Inverter 340...
Page 361: ......