62
STHCkW ed 0409
HERCULES Condensing Export
Technical Documentation
Technical Documentation
Before every intervention:
Check that the gas, water and electricity are correctly connected
to the boiler, according to that indicated in the data plate and
the instruction manual.
Also make sure that:
- the gas valve and boiler parameters are correctly adjusted;
- all devices outside the boiler function and are appropriately
adjusted;
- the external and internal fuses are integral.
Before maintenance interventions or replacement of compo-
nents, remove the electric power supply upstream from the
appliance.
For correct use of the troubleshooting table, on intervention it
is recommended to press the Reset button, switch the boiler off
and remove voltage from the appliance for at least 5 seconds.
This is to allow the boiler to start a new ignition cycle.
Ignition cycle
Ricerca guasti HERCULES Condensing.
CENTRAL HEATING MODE
Press the main button ( ), and then press button A (WINTER).
Turn the central heating selector switch to maximum to prevent domestic
hot water functioning by pressing button B.
N.B.: wait for the completion of any DHW request if the temperature in
the storage tank is below 20°C.
The boiler pump
starts.
N.B.: the display
must show CH
No
Check the presence of the TA jumper on clamps
40-41 of the P.C.B.
N.B.: the jumper must not be present when
external devices are installed such as TA, CAR,
clock programmer, etc...
Check the effective request from any external
devices (TA/CAR programmer clock).
See
error section 31.
No
If present zones digital control unit (as standard
for HERCULES Condensing ABT)
See section F
No
See section B
Yes
The 3-way valve goes
into the CH posi-
tion.
No
See section C
Yes
The zone pump
starts
No
See section G
DOMESTIC HOT WATER MODE
Press the main button ( ), and then press button A (SUMMER).
Turn the DHW selector switch to maximum and open the cock
N.B.: the display must show DHW
The boiler pump starts.
No
See section B
Sì
The 3-way valve goes into the DHW
position.
No
See section C
Apply voltage to the boiler.
The display lights up.
No
See section A
Yes
The error 05 appears on the display
Yes
See error section 05
The error 06 appears on the display
Yes
See error section 15
The error 10 appears on the display
Yes
See error section 10
The error 12 appears on the display
Yes
See error section 12
The error 23 appears on the display
Yes
See error section 23
The error 24 appears on the display
Yes
See error section 24
The error 32 appears on the display
Yes
See error section 32
The error 33 appears on the display
Yes
See error section 33
The error 34 appears on the display
Yes
See error section 34-a
The error 35 appears on the display
Yes
See error section 35-a
The error 37 appears on the display
Yes
See error section 37
No