HERCULES Condensing Export
Technical Documentation
Technical Documentation
Menu configurations M5 (CONFIG).
This menu contains
all configuration options of the boiler functioning parameters
that can be customised. (The first item of the various options that
appears inside the parameter is that selected by default).
M5 Menu (CONFIG)
(an access code must be introduced)
1st Level
2nd Level
Options
Description
Default value
Value
set by the
technician
P53
(POWER)
24 KW
Identifies the output of the boiler on which the P.C.B. is installed
N.B.:
in the case of boiler models called 26 kW set the parameter as:
“OUTPUT 24 KW”.
Equal to boiler
power
Equal
to boiler
power
28 KW
32 KW
P54
(NTC.
TEMP.)
P54.1
DHW NTC1 Display the temperature measured by the probe on the storage tank unit
-
-
P54.2
DHW NTC 2 Not used
-
-
P54.3
NTC 3
The value displayed does not affect this model
-
-
P55
(CALCCHT)
Displays the central heating flow temperature at which the boiler func-
tions, calculated by the controls active on the system heat adjustment
-
-
SERVICE
(BOIL.PAR.)
P57
(PUMP
SPEED)
1
Independently from the options that can be displayed or set, this param-
eter does not effect correct boiler functioning
AUTO
15 K
2
3
AUTO
P62
(MAX SPEED) 4000 ÷ 5500
Set the maximum output depending on the domestic hot water, setting
the speed of the fan (in RPM)
See page 29
P63
(MIN SPEED) 1000 ÷ 1500
Set the minimum output depending on the domestic hot water, setting
the speed of the fan (in RPM)
See page 29
P64
(MAX CH)
≤ P62 (MAX
SPEED)
Set the maximum output depending on room central heating. The value
must be less than or equal to"P62" (MAX. SPEED)
See page 29
P65
(MIN CH)
≥ P63 (MIN
SPEED)
Set the minimum output depending on room heating. The value must be
less than or equal to "P63" (MIN. SPEED)
See page 29
P66
(T.REG.
PAR.)
P66/A
(MIN. CH
T.)
Without the external probe (optional) it defines the minimum flow
temperature. With the external probe present it defines the maximum
flow temperature corresponding to functioning with maximum external
temperature (can be set from 25°C to 50°C)
N.B.:
to continue it is necessary to confirm the parameter (press “D” or
exit from “P66” adjustments by pressing “C”)
25°C
P66/B
(MAX. CH
T.)
Without the external probe (optional) it defines the maximum flow
temperature. With the external probe present it defines the maximum
flow temperature corresponding to functioning with minimum external
temperature (can be set from 50°C to 85°C)
N.B.:
to continue it is necessary to confirm the parameter (press “D” or
exit from “P66” adjustments by pressing “C”)
85°C
P66/C
(MIN. EXT
T.)
With the external probe present it defines at which minimum external
temperature the boiler must function at the maximum flow temperature
(can be set from -20°C to 0°C)
N.B.:
to continue it is necessary to confirm the parameter (press “D” or
exit from “P66” adjustments by pressing “C”)
-5°C
P66/D
(MAX. EXT
T.)
With the external probe present it defines at which maximum external
temperature the boiler must function at the minimum flow temperature
(can be set from 5°C to +25°C)
N.B.:
to continue it is necessary to confirm the parameter (press “D” or
exit from “P66” adjustments by pressing “C”)
25°C