ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Error description
AS-I system errors: error codes E10...E32
243
Error message
Cause(s)
Remedy
E22
Slave 0 detected
The master is in the "protected mode"
and detects a slave with the address 0
on the AS-i bus.
This message is only generated if the
profile of the missing slave on the AS-i
bus is identical to the profile of the slave
with the address 0.
► Change master to "configuration
mode":
operating modes for the AS-i master
selected?
E23
Slave 0 bad profile
The master is in the "protected mode"
and detects a slave with the address 0
on the AS-i bus.
This message is only generated if the
profile of the missing slave on the AS-i
bus is different from the profile of the
slave with the address 0.
► Check and replace slave.
► Project slaves again:
[Menu] > [Quick Setup]
E24
Autoaddress not enabled
The master is in the "protected mode"
and detects a slave with the address 0
on the AS-i bus.
This message is only generated if the
profile of the missing slave on the AS-i
bus is identical to the profile of the slave
with the address 0, the "automatic
addressing" in the master, however,
was not activated.
► Activate "automatic addressing" in
the master:
addressing of individual slaves
E25
Config. error
The master is in the "normal operating
mode" and detects a projection error.
Possible causes:
The profiles of the detected slaves
are different from those of the
projected slaves.
One or more slaves are additionally
detected on the AS-i bus.
One or several slaves are missing
on the AS-i bus.
► Check the detected and projected
slave profile in the menu [Slave
Info].
► Check the entries of slaves in the
lists LAS, LDS, LPS, LPF in the
menu [Slave Lists].
E26
Generic Periphery fault
The master is in the "mormal operating
mode" and detects that at least one
slave on the AS-i bus signals a
periphery fault.