ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Error description
RTS errors: error codes R01...R46
262
Error message
Cause(s)
Remedy
R35
Error in menu text
Possible causes:
1. No data is available in the areas
where menu text is expected.
► Store the menu text data at the
correct area.
2. The expected formatting is not
correct
► Check and correct the formatting.
R36
Error in User Language
Text of the user language is incorrect
► Check and correct the user
language.
R37
Error in text format
The indicated text format is incorrect
► Check and correct the formatting.
R38
Only for AC1353/54
Command Request Eth.-Module
The command for the Ethernet module
could not be executed.
Possible cause:
No communication with the Ethernet
module possible.
► Contact the AS-i specialist or
manufacturer.
R39
Only for AC1353/54
Request Timeout Eth.-Module
Timeout occurred during the execution
of a command of the Ethernet module.
► Repeat command.
R40
Const data checksum failure
A checksum error occurred in the const.
areas (character sets, system language,
user language) of the runtime system.
► Reinstall operating system.
R41
Only for AC1353/54
Zonetimeout DPRAM
Timeout occurred during the
communication between the runtime
system and the Ethernet interface via
DPRAM
► Switch off device for approx. 2 s,
then switch on again.
► If error accours again contact the
AS-i specialist or manufacturer.
R42
State error Eth.-Module
The Ethernet interface has an invalid
status.
→ R41
R43
Zonetimeout Netvar
A timeout occurred during the
communicaton of the network-global
variables between the runtime system
and the Ethernet interface via DPRAM.
→ R41
R44
Invalid AS-i command
The via PLC command channel
requested AS-I command number is not
valid.
► Correct command number