Ideal Viscount GTE -
Installation, Assembly & Servicing
5
INSTALLATION
2.
INSTALLING THE BOILER
2.1 Boiler Location
For the assembly and because of their design, GTE boilers require
no special base or stand and their closed furnace system means
that the floor need not have refractory properties. All you have to
ensure is that the floor can support the weight of the boiler when it
is fitted for operation. If the boiler location is not determined precisely,
leave enough space around the boiler to facilitate monitoring and
maintenance operations.
B
L
M
C
A’
A
0.85 m
min.
0.2
81 m
1.566 m
1.17
2 m
0.195 m
Air outlet
Air inlet
VIS5057
2
1
300
Boiler
body
D min.
(1)
VIS5058
1.
Straight connection (not supplied)
2.
Angled connection (not supplied)
(1)
In order to facilitate subsequent work on the boiler
(replacing the water distributing tube etc.) use a flanged
connection from the boiler to the system, making sure you
comply with minimum clearance dimension
D
.
If
A = 1.2 m
(door opening side),
A’ = 0.5 m
If
A = 0.5 m, A’ = 1.2 m
(door opening side) : adapt the dimensions
on the basis of the dimensions of the burner when the door is
open.
B = 1.5 m :
adapt the dimensions on the basis of the dimensions
of the burner.
GTE
14
15
16
17
18
19
20
21
22
23
24
25
L
2105
2245
2355
2445
2555
2645
2845
2955
3045
3155
3245
3355
M
259
324
269
321
265
299
269
324
269
324
249
303
Cmin.
300
436
436
656
656
656
936
936
936
1266
1266
1266
Dmin.
-
136
136
356
356
356
636
636
636
966
966
966
2.2 Ventilation
The ventilation shall comply with applicable regulations, particularly
codes of practice.
Detailed recommendations for air supply are quoted in B.S. 6644.
Please note :
remember that boilers installed in or close to rooms
in which the atmosphere is polluted with chlorine or fluorine
compounds may be subject to high corrosion.
For example : hairdressing salons, industrial premises (solvents),
cooling equipment, etc.
Boiler installed in such locations shall not be covered by the warranty.