4
Harrier GT Range
- Installation
2.1 INSTALLATION
The minimum dimensions indicated on the following drawing
must be respected to ensure good access around the boiler.
VENTILATION GENERAL
Detailed recommendations for air supply are quoted in BS.
6644. The ventilation requirements in this gas fired boiler
standard are also valid for oil fired boilers of the same heat
input.
Remark: We draw your attention to the risks of corrosion of
boilers which are installed in or near rooms in which the
atmosphere can be polluted by chloride or fluoride
substances E.g.: industrial buildings (solvents), refrigerating
machines, etc...
In these cases, we cannot provide a warranty.
INSTALLATION
Boiler Type
Harrier GT 5
Harrier GT 6
Harrier GT 7
Harrier GT 8
Harrier GT 9
Dimension A
968
1128
1288
1440
1608
Dimension B
Standard control panel
105
Diematic and E control panel
195
Section S cm
2
500
650
800
990
1210
8219-EN-16
* Caution: Pay particular care to the space required for the boiler when the door is open.
For an installationof several boilers side by side, these dimensions need to be modified.