7.1 DELUXE (OPTION) - CONTROL PANEL
All the connections are made to the 2 terminal blocks
provided for this purpose in the control panel.
The connection cables are routed towards the front via the 2
cut outs in the panel behind the boiler, and run in the wiring
duct towards the panel via the two rectangular cut outs of
the front top panel. The sensor cables run on one side, the
cables carrying the 230 V supply on the other and are
supported on both sides by plastic clips.
Caution: the sensor wiring must be kept separate from
the other circuits. Inside the boiler use the 2 cable runs.
Outside the boiler, 2 wiring ducts at least 10 cm apart
should be used.
Wiring is secured in the control panel using cable clips (6
cable clips are supplied in a separate packet) ; these are to
be fitted into the control panel base - see diagram below.
Caution: the maximum current which may be switched by
the outlet is 2 A, cos
ϕ
= 0,7 (= 450 W at the motor of 0.5
méch., hp signal current less than 16 A), if the charge
exceeds one of these values, the control must be relayed
by means of a contractor. The outlet group is protected
by a 5 A fuse.
• Burner connection
Connection of the burner is made using European 7 and 4
pin plugs supplied with the boiler, which simply need to be
fitted into the female plugs supplied with the burners.
To open the control panel