TECHNICAL DATA
10.1 DATA TABLE
Boiler size (no. of sections)
Harrier GT 5
Harrier GT 6
Harrier GT 7
Harrier GT 8
Harrier GT 9
Maximum heat output
kW
140
180
230
280
330
Btu/h x 10
3
477
614
785
955
1126
Minimum heat output
kW
105
140
180
230
280
Btu/h x 10
3
358
477
614
785
955
Combustion chamber
m
3
0.122
0.148
0.174
0.2
0.226
volume
ft
3
4.3
5.2
6.14
7.06
7.98
Flue way volume
m
3
0.206
0.249
0.292
0.335
0.378
ft
3
7.27
8.79
10.31
11.83
13.35
Boiler water content
l
116
136
156
176
196
gal
25.5
29.9
34.3
38.7
43.12
Hydraulic resistance
mbar
10.9
20.4
30
44.5
63.8
at 15 k
in.w.g
4.36
8.16
12
17.8
25.52
Combustion chamber
mbar
0.6
1.1
1.6
2.2
2.5
resistance
in.w.g
0.24
0.44
0.64
0.88
1
Boiler dry weight
kg
608
694
791
886
977
less burner unit
lb
1340
1530
1744
1953
2153
General Data
Boiler size (no. of sections)
Harrier GT 5
Harrier GT 6
Harrier GT 7
Harrier GT 8
Harrier GT 9
Maximum oil rate
l/h
14.26
18.34
23.43
28.53
33.59
gal/h
3.14
4.03
5.16
6.27
7.39
Maximum flue gas volume
l/sec
88.9
114
146
177.5
209.2
ft
3
/min
188.4
241.8
309.6
376.2
443.4
Oil Firing Data
Boiler size (no. of sections)
Harrier GT 5
Harrier GT 6
Harrier GT 7
Harrier GT 8
Harrier GT 9
Maximum gas rate
m
3
/h
14.54
18.7
23.9
29.1
34.3
ft
3
/h
513
660
844
1027
1211
Maximum flue gas volume
m
3
/sec
0.087
0.11
0.14
0.17
0.2
ft
3
/min
184.3
233
296
360
424
Gas Firing Data
Data Notes
Fuel rates and flue gas data relates to maximum outputs ratings.
Gas firing data relates to the use of NATURAL GAS ONLY.
Details for the use of LPG are available, on request, to Caradon Ideal Ltd.
The gas rate at calorific values differing from the standard quoted above may be calculated by direct proportion.
CALORIFIC VALUE; 38.5 MJ/m
3
(1035 btu/ft
3
).