background image

CGS 2 and CGS 3 

LIQUID / GASEOUS FUEL 

STEEL BOILER 

USER MANUAL 

Summary of Contents for CGS2 Series

Page 1: ...CGS 2 and CGS 3 LIQUID GASEOUS FUEL STEEL BOILER USER MANUAL ...

Page 2: ...Code No A 4 1 8 Revision 250718 Book Print Date 250718 ...

Page 3: ...CGS 2 and CGS 3 LIQUID GASEOUS FUEL STEEL BOILER Installation Commissioning Operation and Maintenance Manual ...

Page 4: ......

Page 5: ... Temperature and Room Temperature 13 Settings Main Parts of the Boiler CGS2 16 Main Parts of the Boiler CGS3 17 Installation 18 Safety Systems 21 Burner Selection 26 Burner Installation 26 Suitable Fuels 28 Flue Gas System 28 Heating System Filling and Feeding Water 29 Features Oxygen Corrosion 30 Commissioning 31 Start Up and Stop 34 ...

Page 6: ...gram 47 Ecopanel 7 21 and 12 311 Electrical Diagram 48 Heating Control Panel SDC Easy Operation Guide 49 Boiler Label Information 59 Technical Specifications Table 60 Burner Selection Table 62 Burner Gas Line Diagram 65 Control and Commissioning Form 66 CGS Steel Boiler Flue Information 67 ...

Page 7: ... adjustment or maintenance Have your device installed by ALARKO CARRIER Authorized Dealers Our Authorized Dealers and Services will provide you with the necessary information about how to use and maintain the device after they have placed made connections of and put into operation of your device You can ask the issues you don t understand over and over again Our experts will be happy to answer you...

Page 8: ...ns and are selected to withstand the chemical mechanical and thermal effects to which they may be exposed during the expected lifetime There is no soft soldering on gas bearing parts The security of the changeable settings is ensured Asbestos materials are not used There are no parts in contact with the food and or water used for sanitary purposes in our boilers Used parts are CE marking approved ...

Page 9: ...uel or EN 267 liquid fuel certified burners to operate in accordance with the Directive 92 42 AT on Efficiency Requirements for Boilers and the Directive 2009 142 EC on Appliances Burning Gaseous Fuels This is a B23 type boiler so the boiler must be connected to a flue with sufficient draught in accordance with the regulations and there should be no flue gas leakage into the boiler room During the...

Page 10: ...tch in a suitable place outside the boiler room This switch must be able to stop the combustion process or fuel supply It is useful to specify it with a nameplate When starting up a newly installed system initial checks and commissioning must be performed by the Alarko Carrier Authorized Service Maintenance is the responsibility of the user and must be performed by an authorized service If you wis...

Page 11: ...ice from whom you purchase the products and sent to the ALARKO CARRIER Please follow ALARKO CARRIER Authorized Services are at your service at any time even in the slightest problems You can find authorized service addresses in the Authorized Service Address Booklet supplied with your device Any defects arising from improper installation maintenance or use shall not be covered by the warranty Malf...

Page 12: ...els you can use If you want to change the fuel that has been commissioned for the first time contact our authorized services The boiler can be used in both open and closed expansion systems A suitable expansion system in the system should work actively at all times In the 2nd transition pipe in CGS2 boilers and 3rd transition pipe in CGS3 boilers there are turbulators to increase the heat transfer...

Page 13: ...gram and saves them to the eco panel The boiler then operates automatically depending on the outside temperature With the tests to be carried out in 1 or 2 weeks it should be determined whether the values determined at the beginning are suitable for the conditions of the building and suitable values for building should be found As long as it is not changed by the user the eco panel works according...

Page 14: ...urves are the graphs in which the boiler water temperature is determined depending on the desired room temperature and the outside temperature Boiler water temperature o C Outside temperature oC Room temperature oC ...

Page 15: ... temperature is desired to be 25 C or 15 C the way of change of the heating curve of 1 5 is indicated by dashed lines Curve of 1 5 for 25 C room temperature Curve of 1 5 for 20 C room temperature Curve of 1 5 for 15 C room temperature Boiler water temperature o C Outside temperature oC Room temperature oC ...

Page 16: ...er 2 Boiler return flange 10 Rear fume cupboard 3 Flow safety connection 11 Fume transition pipes 4 Return safety connection 12 Flue connection outlet 5 Hydrometer connection 13 Cleaning cover 6 Thermometer connection 14 Blowout cover 7 Condensate drain connection 15 Carrier frame 8 Burner connection cover 16 Boiler feet ...

Page 17: ...er return flange 11 Front fume cover 3 Flow safety connection 12 Rear fume cupboard 4 Return safety connection 13 Flue connection outlet 5 Hydrometer connection 14 Cleaning cover 6 Thermometer connection 15 Blowout cover 7 Condensate drain connection 16 Carrier frame 8 III Fume Extractor Pipes 17 Boiler feet 9 II Fume Extractor Pipes ...

Page 18: ...oom All equipment and control system of the heating system should be able to provide the specified heating loads according to the external climatic conditions and the desired internal temperature It should be able to protect the heating system against freezing and humidity when normal operating conditions comfort temperature level are not required The equipment for the control and safety systems o...

Page 19: ...ion and the fuel line must be cut automatically when the fuel leakage reaches a certain level If the system is to be commissioned with liquid fuel the turbulators in the smoke ducts must be removed Turbulators are for use with gaseous fuel Since the turbulators are not used the boiler efficiency will decrease by 2 5 All electrical connections must be made according to current standards and accordi...

Page 20: ...asket and adapter plate If the gap between the burner barrel and the boiler refractory is more than 10 mm this area must be filled tightly with 1200 C resistant ceramic fiber material The responsibility for the installation and commissioning of the control and safety system of the heating system in compliance with the applicable standards and regulations is in the units that implement the system p...

Page 21: ...optional control panel is not supplied this controller must be supplied and installed by the installer Protection against exceeding the maximum operating pressure Each boiler control circuit must have at least one pressure relief valve The pressure relief valve must protect the system from high pressure by opening before the boiler exceeds its operating pressure and the system pressure should neve...

Page 22: ...in the equipment supplied with the boiler and the project and assembly units are responsible for the selection and installation of the equipment Closed expansion tank In closed heating systems the water which is in the system as the heat carrier tries to expand and increase inherently when heated this causes the pressure increase due to the fact that there is no volume change in closed systems In ...

Page 23: ... 9 and or bear CE marking Water temperature gauge thermometer The boiler must be more than 20 of its maximum operating temperature The boiler must be installed in the flow line the water temperature gauge in the boiler return line is not required by the standards but is recommended by us All optional boiler control panels have a water temperature gauge Boiler thermometer If the optional control pa...

Page 24: ...must be connected to the connection located under the boiler flow and return water flange Manual shut off equipment must not be used in the connection line between the expansion tank and the boiler There should be a ventilation outlet and overflow pipe which can not be closed in the expansion tanks open to the atmosphere The overflow pipe should be dimensioned to drain the maximum flow rate of the...

Page 25: ...ntrol panels have a water temperature gauge Boiler thermometer If the optional control panel is not supplied water temperature gauge must be supplied and installed by the installer Water temperature controller Boiler thermostat There must be a controller which controls and regulates the water temperature required by the heating system This temperature cannot be above the adjustable maximum setting...

Page 26: ...in compliance with the applicable TS EN standards BURNER INSTALLATION The burner must be connected to the boiler body by using the burner adapter plate available on the front cover as standard Actions to be made are as follows 1 Remove the burner adapter plate bolts and remove the adapter plate from the boiler cover Figure x Figure x Burner Adapter Plate Burner Adapter Plate Burner Gasket 2 Open t...

Page 27: ...gth of the combustion head is too long or too short get approval from the boiler manufacturer for trouble free operation If the gap between the burner combustion head diameter and the refractory in the boiler front cover is more than 10 mm fill the remaining gap firmly with the heat insulation material supplied with the boiler The burner flange connection must always be mounted so as not to cause ...

Page 28: ...ioned with liquid fuel the turbulators in the smoke ducts must be removed Turbulators are for use with gaseous fuel Since the turbulators are not used the boiler efficiency will decrease by 2 5 There must be a draught between 0 and 0 3 mbar at the flue gas outlet of the boiler For reference some tables related to this matter are given in the appendix The effective flue height is the difference in ...

Page 29: ...ts for feeding water and boiler water quality VDI 2035 Part 1 December 2005 Association of German Engineers Prevention of damage in water heating installations Scale formation in drinking water If the heating system includes units made of material other than steel e g aluminum radiator copper pipe these units may require lower pH and conductivity but the protection of the boiler is a priority in t...

Page 30: ... below a Continuous supply of fresh water to the system b Using plastic pipes without oxygen barrier c Using an open expansion tank d Air entering from vacuum forming areas If it is not possible to remove the above factors in the heating installation the boiler and the installation must be separated from each other by a plate heat exchanger Damages caused by the presence of oxygen in the boiler wa...

Page 31: ...obstruction The flue gas ducts and the flue are adequate and installed correctly Ensure that all system controls and safety equipment are available have the correct properties and are installed correctly and that they are all operating in the desired range of values Fuel type and burner capacity are selected correctly according to boiler and heating system requirements If gaseous fuel is used the ...

Page 32: ...and setting values of the selected low water level control system without filling the system completely Deaerate all possible points of the system Switch on the circulation pump and check that it operates in the correct direction and circulates the water Deaerate the system again If the water level pressure has dropped supply water again In open expansion systems tick up the lower pressure from th...

Page 33: ...0 260 LPG 1 9 10 100 1070 230 260 Diesel ______ 1 ______ ___ 11 ____ 13 110 110 250 250 Note Flue emission values must be in accordance with applicable regulations The values given in parentheses are taken from the Regulation on Control of Air Pollution Due to Heating of Turkish Ministry of Environment and Forestry After adjusting the burner continue to burn the burner and check that the 1st and i...

Page 34: ...EAKAGE Do not activate the system Do not start fire Do not touch any electrical unit including plugs light switch Do not smoke Do not use any phones in the building where the leak occurs Close the main fuel valve entering the building Warn and evacuate other people in the building Contact your local authorities through your neighbor s phone immediately If you have not detected any fuel leakage Che...

Page 35: ...p Standard control panel a If there is a 2nd stage thermostat in your control panel first set the 2nd stage thermostat to minimum If the thermostat is operating normally the burner will immediately switch to 1st stage operation This function is a practical way to control the 2nd stage thermostat If the control panel is single stage start from the section b b Set the boiler thermostat to minimum If...

Page 36: ... the system is operating with liquid fuel the boiler heat transfer surfaces should be cleaned at least once a month The cleaning frequency depends on the operating characteristics and combustion parameters The need for cleaning may occur in much shorter times due to some factors such as poor combustion setting or the use of a bad fuel insufficient flue draught The occurrence of soot with a thickne...

Page 37: ...in the first 1 2 attempts it will be activated when the air in the fuel line is bled Call your authorized service at least once a year to have them to control of the combustion parameters safety and control devices Call your authorized service at least once a year to have them to control of the combustion parameters safety and control devices When the burner failures please check the following bef...

Page 38: ...stone can lead to reduced system efficiency in the short term and permanent damage to the boiler in the long term Check your safety and control devices periodically Wet rotor pumps not operated for long term summer period may have a locking problem due to corrosion Operate the wet rotor pumps in the system once a month for 5 minutes to prevent locking The frequent need for feed water and the frequ...

Page 39: ...t 100 C 3 Boiler Temperature Gauge 30 120 C 4 Main Control Switch 5 Control Panel Energy Lamp Pump Running Lamp 6 Limit Thermostat Fault Lamp 7 First and Second Stage Thermostats Eco panel PE 7 21 or PE 12 31 1 Control Panel Fuse 6 A 2 Safety Limit Thermostat 100 C 3 Boiler Temperature Gauge 0 120 C 4 Main Control Switch 0 1 5 Control Panel Energy Lamp Pump Running Lamp 6 Limit Thermostat Fault La...

Page 40: ...fety limit thermostat Boiler thermostat Thermometer 0 120 C Manometer 6 bar Max pressure limiter Min pressure limiter Relief valve Blow off valve Lock valve Pressure regulator Check valve non return valve Cold water meter Automatic filling system Drain valve HS SP ACP MET 3WV TC TC Tl P SPL1 SPL2 sv FT IV PR cv M ARFS DV SAFETY EQUIPMENT AND HYDRAULIC DIAGRAM FOR SYSTEMS WITH CLOSED EXPANSION TANK...

Page 41: ... way valve Safety limit thermostat Boiler thermostat Thermometer Hydrometer Low pressure switch Lock valve Valve Pressure regulator Check valve non return valve Drain valve Safety flow pipe Safety return pipe Overflow pipe Ventilation pipe HS SP BPP OEC 3WV TCL TC Tl HM WLI LV v PR CV DV GB DB TB HB SAFETY EQUIPMENT AND HYDRAULIC DIAGRAM FOR SYSTEMS WITH OPEN EXPANSION TANK BOILER ...

Page 42: ...ed with the boiler 2 Observe the size of the burner connection bolts Bolt length should not exceed the total thickness of the burner connection flange gasket and burner adapter plate 3 The burner barrel pipe should pass the inner alignment of the cover at a distance of 50 100 mm Burner adapter plate Burner barrel insulation Ceramic wool Rock wool Rock wool Ceramic wool must be 50 100 mm ...

Page 43: ...70 CGS2 700 1310 1970 CGS2 800 1310 1970 Model B mm C mm CGS3 100 680 1050 CGS3 125 680 1150 CGS3 150 680 1300 CGS3 175 750 1300 CGS3 200 750 1400 CGS3 250 750 1450 CGS3 300 750 1500 CGS3 350 880 1560 CGS3 400 880 1670 CGS3 450 880 1750 CGS3 500 960 1860 CGS3 600 1050 1900 CGS3 700 1050 2000 CGS3 800 1090 2130 CGS 3 1000 3000 BOILERS Model B mm C mm CGS3 1000 1100 2000 CGS3 1250 1100 2000 CGS3 150...

Page 44: ...er length B Min 600 mm W M in A 100 mm D L 2 500 L Boiler length H Boiler room height should be at least Boiler height 12000 mm Note These dimensions are recommended reference values They may vary according to local standards ...

Page 45: ...45 Rated Heat Power kW FOR SQUARE SECTION PLEVVA Effective Flue System Height m Inner Diameter ...

Page 46: ...46 Rated Heat Power kW CIRCULAR SECTION SCHIEDEL Effective Flue System Height m ...

Page 47: ...ERMOSTAT OUTLET 2ND STAGE THERMOSTAT INLET 2ND STAGE THERMOSTAT OUTLET NEUTRAL RESET INLET RESET OUTLET IL ON OFF SWITCH TS SAFETY THERMOSTAT TC 1 1ST STAGE THERMOSTAT TC 2 2ND STAGE THERMOSTAT L1 FAULT LAMP L2 1ST STAGE THERMOSTAT RUNNING LAMP L3 2ND STAGE THERMOSTAT RUNNING LAMP F 6 3 AMP FUSE ...

Page 48: ...AMP KT1 1ST STAGE BOILER THERMOSTAT 16 17 18 2ND STAGE BOILER THERMOSTAT G SENSOR JOINT TERMINALS N NEUTRAL L PHASE AF OUTDOOR AIR SENSOR WF KF BOILER SENSOR SF BOILER SENSOR VF1 MIXTURE CIRCUIT SENSOR 1ST ZONE VF2 MIXTURE CIRCUIT SENSOR 2ND ZONE P2 2ND ZONE MIXTURE CIRCUIT PUMP 13 14 2ND ZONE 3 WAY VALVE ON OFF PHASES P1 1ST ZONE MIXTURE CIRCUIT PUMP 7 8 1ST ZONE 3 WAY VALVE ON OFF PHASES BP BOIL...

Page 49: ...tton 8 Economy temperature button 9 Domestic water temperature button KSS 10 Entry button push turn 11 Symbols of operating modes Heating programs Entry button push turn General functions Nominal values and parameters selected using the entry button can be changed and then saved by pressing it Various programs can be selected by turning the entry button Right The setting value increases turn Left ...

Page 50: ...g mode which is active at that moment Special indicators Ice crystal symbol System frost protection active Parasol symbol Summer mode active Heating system off KSS running as programmed Error Message Ex KSS appears alternately with the standard indicator Contact an authorized service Emission measurement In heating system control panels for service only press the button Current boiler water temper...

Page 51: ...perature Current actual value desired setting value flashes Set the boiler water temperature to the desired value Automatic recommissioning press the button Setting the day room temperature press the button Changing the temperature Setting range 5 to 30 C Application of change or or automatic depending on the duration of the set information Setting the economy temperature press the button Changing...

Page 52: ...ration of the set information Heating curves The heating power through the heating curves is adapted based on the structural properties of the building from the relevant outside temperature Correction of vertical fluctuations in the heating curve Entering the menu Press and hold this button for about 3 seconds Selecting the heating circuit DD Direct heating circuit KD1 Mixture Circuit 1 KD2 Mixtur...

Page 53: ...urs program According to the working hours program only domestic water is active The heating system is disabled for frost protection AUTOMATIC SUMMER 3 Continuous programs HEATING ECO HEATING Continuous heating operation without time limit Continuous heating operation in economic operating mode without time limit Disabling the heating system and domestic water for frost protection STANDBY Selectin...

Page 54: ...button and select the option PARTY END Application of change or Changing the time Application of time or 4 Holiday programs Holiday programs can be selected by pressing button HOLIDAY Disabling the heating system for frost protection or low power operation of the heating system during the holiday period The domestic water temperature is disabled for frost protection Example Press the holiday progr...

Page 55: ...puts Meters and consumption data Heating circuit information e g Program type HOLIDAY OUTSIDE RETURN HOME PARTY END AUTOMATIC etc Current operating hours programs P1 or P1 P3 depending on activation Operating Mode Daytime operation low power operation disabling operation Heating circuit depending on the model of the device DD Direct heating circuit KD1 Mixture Circuit 1 KD2 Mixture Circuit 2 KSS D...

Page 56: ... the previous selection is made by pressing the button By pressing the return to the standard screen button or according to the set duration of information it is made automatically 1 Selecting the circuit Restoring and copying of standard programs Setting range Direct heating circuit DD Mixture circuit 1 KD1 Mixture circuit 2 KD2 Domestic water circuit KSS standard programs copying of heating circ...

Page 57: ...INFORMATION When the second cycle is also completed a third cycle is available for use Continue 4 Start of heating Activation time Setting range Between 0 00 24 00 hours INFORMATION The activation time is shown in the top clock tab via a flashing section Continue 5 End of Heating Deactivation time Setting range Between 0 00 24 00 hours INFORMATION The deactivation time is shown in the top clock ta...

Page 58: ...tic water temperature ATTENTION When the desired daytime room temperature or domestic water temperature is changed using the buttons or all the relevant cycle temperatures are changed accordingly and at the same value Continue 7 Day and heating cycle selection copying Block creation If necessary select the next heating cycle or day as described in Step 3 below and adjust accordingly ...

Page 59: ...CITY kcal hFUEL CATEGORY MAX OPERATING PRESSURE bar DATE OF MANUFACTURE MAX OPERATING TEMPERATURE CSERIAL NO 2ND BOILERS WITH A CAPACITY OF 1000 KW AND ABOVE www alarko carrier com tr Email info alarko carrier com tr İSTANBUL GOSB GebzeOrganize Sanayi Bölgesi Ş Bilgisu Cad Gebze 41480 KOCAELİ Phone 0262 648 6000 Fax 0262 648 6101 ANKARA Sedat Simavi Sok No 48 Çankaya 06550 ANKARA Phone 0312 409 52...

Page 60: ...6 CGS2 300 300 349 324 376 1 4 0 14 1 1 2 1 1 2 790 347 566 340 CGS2 250 250 291 270 314 1 6 0 14 1 1 2 1 1 2 712 293 471 283 CGS2 200 200 233 216 251 1 4 0 12 1 1 2 1 1 2 552 234 378 227 CGS2 150 150 174 162 188 1 2 0 10 1 1 4 1 1 4 447 139 284 170 CGS2 125 125 145 135 157 0 6 0 10 407 151 237 142 CGS2 100 100 116 108 125 0 6 0 06 352 141 188 113 Unit kcal h x 1000 kcal h x 1000 bar mbar mbar mSS...

Page 61: ...85 130 753 452 CGS3 3 50 350 407 378 439 92 7 1 8 0 08 NW80 NW80 1 1 2 1 1 2 950 600 185 130 660 396 CGS3 3 00 300 349 324 376 92 7 1 8 0 07 NW80 NW80 1 1 2 1 1 2 880 525 185 130 566 340 CGS3 2 50 250 291 270 314 92 7 1 4 0 07 NW65 NW65 1 1 2 1 1 2 805 460 185 130 471 283 CGS3 2 00 200 233 216 251 92 7 1 2 0 06 NW65 NW65 1 1 4 1 1 4 650 440 185 130 378 227 CGS3 1 75 180 209 194 226 92 7 1 2 0 06 N...

Page 62: ... 60 2 3 4 ALG 60 2 3 4 Flange Diamet er mm 115 115 Single Stage with Damper Motor ALG 16DM 1 2 ALG 16DM 1 2 21 mbar Flange Diamete r mm 190 190 190 190 190 190 190 190 256 190 190 190 190 190 190 190 190 256 Modulating ALG 60 M 1 1 4 MBC 300 ALG 60 M 1 1 4 MBC 300 ALG 60 M 1 1 4 MBC 300 ALG 60 M 2 MBC 700 ALG 60 M 2 MBC 700 ALG 77 M 2 MBC 700 ALG 94 M 2 MBC 1200 ALG 94 M 2 MBC 1200 ALG 120 M 2 MBC...

Page 63: ... 162 162 185 185 Single Stage ALF 12 ALF 24 ALF 24 ALF 24 ALF 42 ALF 42 ALF 42 ALF 65 ALF 65 ALF 12 ALF 24 ALF 24 ALF 24 ALF 42 ALF 42 ALF 42 ALF 65 ALF 65 Flange Diamet er mm 145 160 165 165 165 165 184 184 230 145 160 162 162 162 162 184 184 230 Diesel Burner Two Stage ALM 30 2 ALM 40 2 ALM 60 2 ALM 60 2 ALM 60 2 ALM 60 2 ALM 76 2 ALM 76 2 ALM 125 2 ALM 30 2 ALM 40 2 ALM 60 2 ALM 60 2 ALM 60 2 A...

Page 64: ...S3 1250 1 453 ALG 200 M MBC 3100 256 ALG 200 M M BC 700 256 240 ALM 174 2 230 ALF 180 2 230 RMS9 VMDU 278 CGS3 1500 1 744 ALM 174 2 230 ALF 180 2 230 RMS9 VMDU 278 CGS3 1750 2 034 L9 VZDU 278 MS9 VZDU 278 RMS9 VMDU 278 CGS3 2000 2 325 L9 VZDU 278 MS9 VZDU 278 RMS9 VMDU 278 CGS3 2500 2 907 L9 VZDU 278 MS10 VZDU 278 RMS10 VMDU 278 CGS3 3000 3 488 L10 VZDU 278 MS10 VZDU 278 RMS10 VMDU 278 Note The bu...

Page 65: ... Flexible Coupling Optional 10 Gas Sealing Unit optional for small capacity burners 3 Gas Line Inlet Pressure Measuring Point of less than 1200 kW 4 Gas Filter 11 Air Pressure Switch 5 Minimum Gas Pressure Switch 12 Burner Gas Pressure Measuring Point 6 Safety Solenoid Valve 13 Burner 7 Gas Pressure Regulator 14 Regulator Output Pressure Measuring Point 8 Operating Solenoid Valve 15 Gas Line Outpu...

Page 66: ...urner installation is adequate The entrance of the barrel into the boiler is adequate A carrier support under the burner is available adequate cm CLOSED EXPANSION TANK Connection diameter is adequate finger No valve in the connection line to the boiler Tank volume is adequate liter Gas pressure was measured when the tank was empty adequate FLUE SYSTEM Boiler flue connection is adequate Number of e...

Page 67: ...0 1 0 350 350 CGS 3 100 116 35 125 38 10 10 47 28 190 120 0 1 0 0 1 0 150 150 CGS 3 125 145 44 157 47 10 10 60 35 190 120 0 1 0 0 1 0 150 150 CGS 3 150 174 52 188 56 10 10 71 42 190 120 0 1 0 0 1 0 150 150 CGS 3 200 233 70 251 75 10 10 95 57 190 120 0 1 0 0 1 0 200 200 CGS 3 250 291 87 314 94 10 10 117 71 190 120 0 1 0 0 1 0 200 200 CGS 3 300 349 105 376 113 10 10 141 85 190 120 0 1 0 0 1 0 250 25...

Page 68: ... 0312 440 79 30 İZMİR Şehit Fethibey Cad No 55 Kat 13 35210 Pasaport İZMİR Phone 0232 483 25 60 Fax 0232 441 55 13 ADANA Ziyapaşa Bulvarı Çelik Ap No 25 5 6 01130 ADANA Phone 0322 457 62 23 Fax 0322 453 05 84 ANTALYA Mehmetçik Mahallesi Aspendos Bulvarı No 79 5 ANTALYA Phone 0242 322 00 29 Fax 0242 322 87 66 MDH 444 0 128 web www alarko carrier com tr e mail info alarko carrier com tr ...