Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
65-
P23.12
Detection value of too
large speed deviation
0.0%
~
100.0%(motor rated frequency)
20.0%
☆
P23.13
Detection value of too
large speed deviation
0.0s
~
30.0s
0.0
:
shielding
0.0s
☆
P23.14
Input phase loss
detection time
0.0s
~
30.0s
0.0
:
forbidden
8.0s
☆
P23.15
Output phase loss
inbalance detecting
0%
~
100%
30%
☆
P23.18
Fault protection action
selection 1
Unit’s digit : input phase loss
0: coast to stop
1: Emergent stop
2: Stop as per stop mode
3: continue to Run
Ten’unit: user self-defined fault 1
same as Unit’s digit
Hundred’unit: user self-defined fault 2
same as Unit’digit
Thousand’s unit: communication fault
same as unit’s digit
0000
☆
P23.19
Fault protection action
selection 2
Unit’s digit: motor overload
0: coast to stop
1: emergent stop
2: stop as per stop mode
3: continue to run
Ten’unit: motor overheat
same as unit’digit
Hundred’unit: too large speed deviation
same as unit’digit
Thousand’s unit: motor over speed
same as Unit’digit
0000
☆
P23.20
Fault protection action
selection 3
Unit’s digit: PID feedback lost during running
0: coast to stop
1: fast stop
2: stop as per stop mode
3: continue to run
Ten’unit: Reserved
same as unit’digit
Hundred’unit: reserved
same as unit’digit
thousand’unit: reserved
same as unit’digit
0000
☆
P23.21
Fault protection action
selection 4
Unit’s digit: output phase loss
0: coast to stop
1: fast stop
2: stop as per stop mode
Ten’unit: EEPROM fault
0: coast to stop
0000
☆