ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 78
-
P40.39
PID operation at
stop
0-
No PID operation at stop
1-
PID operation at stop
0
☆
P40.40
PID command
for accel and
decel time
0.0s
~
6000.0s
0.0s
☆
P40.41
PID offset
selection
0-digital setting
1-AI1
2-
AI2
3-
AI3(option card)
0
☆
P40.42
PID offset digital
setting
-100.0%
~
100.0%
0.0%
☆
41 Group Sleeping function
P41.00
Sleep mode and
wake up
selection
Unit’s digit: sleep mode selection
0:no sleep function
1:sleep by frequency
2:AI1 sleep (AI1 as pressure feedback)
3:AI2 sleep(AI2 as pressure feedback)
Ten’s digit :wake up mode selection
0:wake up by frequency
1:AI1 wake up (AI1 as pressure
feedback)
2:AI2 wake up (AI2 as pressure
feedback)
Hundred’s digit :
0: positive direction
Feedback big then sleep, feedback small
then wake up, P41.04 < P41.03
During running, pressure feedback > P41.03,
the inverter sleeps When sleeping, pressure
feedback < P41.04, the inverter wakes up
1: reverse direction
Feedback small then sleep, feedback big
then wake up, P41.04 > P41.03
During running, pressure feedback < P41.03,
inverter sleep When sleeping, pressure
feedback > P41.04, the inverter wakes up
Normally, the frequency source is PID
setting, and sleep by frequency wake-
up direction is the same as the PID
action direction P40.14.
Sincethe
parameter
setting
is
unreasonable,
when
the
wake-up
condition enables, even if the sleep
condition is established, the sleep mode
cannot be activated, and Pay special
attention to avoid accident when use
00
☆