11 Group Motor 1 Parameter
P11.00
Motor type
0
:
AC asynchronous motor
1
:
Synchronous motor(Special software)
See appendix parameter
0
●
P11.02
Motor rated power
0.1kW
~
800.0kW
when power is less than 1kw ,0.75kw set
to 0.8 as per round up principle ,0.55kw
motor set 0.6
when change motor rated power,AC drive
will automatically set other parameter of
motor name plate and motor model
parameter
be careful to use
Depend
★
P11.03
Motor rated voltage
10V
~
2000V
Depend
★
P11.04
Motor rated current
P11.02<30kW
:
0.01A
P11.02>=30kW
:
0.1A
Depend
★
P11.05
Motor rated frequency
1.00Hz
~
600.00Hz
50.00Hz
★
P11.06
Motor rated RPM
1
~
60000rpm
Depend
★
P11.07
Motor rated power factor
0.500
~
1.000
Depend
★
r11.08
Motor rated torque
Read only,0.1Nm(P11.02<30KW);
1Nm(P11.02>30KW)
-
●
r11.09
Number of motor 1 pairs of
pole
Read only,It will auto calculate as per motor
rated frequency and rated rotating speed
-
●
P11.10
Auto-tune/self-learning
0
:
no auto tuning
1
:
Stationary auto tuning of Asynchronous
motor
2
:
Rotational auto tuning of Asynchronous
motor
0
★
1: Stationary auto tuning of Asynchronous motor
When do auto tuning ,motor stationary ,it can get parameter P11.11
~
P11.13
。
Static self-learning can not learn all the motor parameters, so the control performance is difficult to achieve the
best; if the motor nameplate information is incomplete, or the motor is not a 4-pole 50Hz GB motor, it is
recommended to perform "rotation self-learning".
In the case of limited rotation, such as limited travel, limited load (crane), limited running direction, etc., static
self-learning is used.
2: Rotatoinal auto tuning of Asynchronous motor
When do auto tuning ,motor first stationary and rotary, ,it can get parameter P11.11
~
P11.18
,
as to close loop
contro,it can get P10.03 encoder directioin
When rotating self-learning, the motor will rotate forward and the speed can reach 50%~100% of the rated
speed. The lighter the load during self-learning, the better the learning effect.
note:
Notice:
it can do motor auto tune when command source is keypad
Please self-learn when the motor is cold. Make sure the motor is at rest before learning!
Please confirm that the motor nameplate parameters have been set before self-learning. For closed-loop control,
you should also set the encoder parameters!
After setting this parameter, press the
“RUN”
button on the keyboard, the self-learning will start, and the inverter
will stop itself after the self-learning is completed.