ICON500
high performance vector control frequency inverter user
manual
Chapter2 production information
-
5-
ICON500-030G/037PT4
40
62.0
60.0
75.0
30
SIZE E
optio
n
ICON500-037G/045PT4
50
76.0
75.0
87.0
37
ICON500-045G/055PT4
60
92.0
90.0
110.0
45
SIZE F
ICON500-055G/075PT4
85
113.0
112.0
135.0
55
ICON500-075G/090PT4
104
157.0
152.0
165.0
75
SIZE G
ICON500-090G/110PT4
112
170.0
176.0
210.0
90
Technical Specifications
Table 2-2 ICON500 Technical Specifications
Item
Specifiation
Input
Inuput Voltage
1phase/3phase 220V
:
200V
~
240V
3 phase 380V-480V
:
380V
~
480V
Allowed Voltage
fluctuation range
-15%
~
10%
Input frequency
50Hz / 60Hz
,
fluctuation less than 5%
Output
Output Voltage
3phase
:
0
~
input voltage
Overload capacity
General purpose application
:
60S for 150% of the rated current
Light load application
:
60S for 120% of the rated current
Control
Control mode
V/f control
Sensorless flux vector control without PG card
(
SVC
)
Sensor speed flux vector control with PG card (VC)
Operating mode
Speed control
、
Torque control
(
SVC and VC
)
Speed range
1:100 (V/f)
1:200( SVC)
1:1000 (VC)
Speed control
accuracy
±0.5% (V/f)
±0.2% (SVC)
±0.02% (VC)
Speed response
5Hz(V/f)
20Hz(SVC)
50Hz(VC)
frequency range
0.00
~
600.00Hz(V/f)
0.00
~
200.00Hz(SVC)
0.00
~
400.00Hz(VC)
Input frequency
resolution
Digital setting: 0.01 Hz
Analog setting: maximum frequency x 0.1%
Startup torque
150%/0.5Hz(V/f)
180%/0.25Hz(SVC)
200%/0Hz(VC)
Torque control
accuracy
SVC
:
within 5Hz10%
,
above 5Hz5%
VC:3.0%
V/f curve
V / f curve type: straight line, multipoint, power function, V / f separation
Torque boost support: Automatic torque boost (factory setting), manual
torque boost
Frequency giving
ramp
Support linear and S curve acceleration and deceleration;
4 groups of acceleration and deceleration time, setting range 0.00s ~
60000s
DC bus voltage
control
Overvoltage stall control: limit the power generation of the motor by
adjusting the output frequency to avoid skipping the voltage fault;