Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
49-
08 Group Digital output setting
P08.00
Frequency detection value
(FDT1)
0.00Hz
~
maximum frequency(P01.06)
50.00Hz
☆
P08.01
Frequency detection
hysteresis 1
0.0%
~
100.0% FDT1
5.0%
☆
P08.02
Frequency detection value
2(FDT2)
0.00Hz
~
maximum frequency(P01.06)
50.00Hz
☆
P08.03
Frequency detection
hysteresis 2
0.0%
~
100.0% FDT2(P08.02)
5.0%
☆
FDT is used to check inverter output frequency,when output frequency is greater than frequency detection
value,FDT effective,when output frequency is less than frequency detection value*(1- Frequency detection
hysteresis),FDT ineffective;whenoutput frequency is between the above two,FDT output keep no
change,following is FDT chart
Output
frequency
P08.00
P08.00 P×08.01
FDT
time
suatus
valid
invalid
invalid
time
P08.04
Detection range of
frequency arrival
0.0%
~
100.0% maximum frequency (P01.06)
When output frequency is between command
frequency ±P08.04*P01.06,corresponding DO
output effective signal
3.0%
☆
P08.05
Desired frequency attained
1
0.00Hz
~
maximum frequency (P01.06)
50.00Hz
☆
P08.06
Any frequency reaching
detection amplitude 1
0.0%
~
100.0% maximum frequency (P01.06)
3.0%
☆
P08.07
Desired frequency
attained2
0.00Hz
~
maximum frequency(P01.06)
50.00Hz
☆
P08.08
Any frequency reaching
detection amplitude 2
0.0%
~
100.0% maximum frequency (P01.06)
3.0%
☆
P08.09
Zero speed detection
amplitude
0.00H
~
5.00Hz
0.25Hz
☆
P08.10
Zero current detection
level
0.0%
~
100.0% rated motor current
5.0%
☆
P08.11
Zero current detection
delay time
0.000
~
30.000s
0.000
~
30.000s
Notice
:
When output current≤P08.10 and endure
P08.11 time,corresponding DO output effective
signal
0.100s
☆