ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 32
-
Functio
n code
Parameter name
Description
Default
Property
P01.19
Multi-step speed
reference source
Unit’digit
:
0 phase reference source
set by
0-multi-step speed(P01.21)
1-preset frequency (P00.07)
2:AI1
3:AI2
4:Reserved
5:Reserved
6:HDI pulse
7:Communication
8:PID
Ten’s digit
:
Combination of multiple speed
0
:
Combination methord
1
:
Priority method
00
★
K1-K4 Each represent DI multiple terminal 1-4 status ,O represent ineffective ,1 represent effective,M indicates
current output number of speed.Instructions of multiple speed combination
0: Combination method
M = K1 + (K2*2) + (K3*4) + (K4*8)
For example: K0=1,K1=0,K2=1,K3=0,Then M=5
,
current output fifth phase speed
1: Priority method Multiple step speed output 0
~
4 phase speed
,
Priority K4
>
K3
>
K2
>
K1
。
For example: K4=1, then M=4;
K4=0,K3=1,then M=3;
K4=0,K3=0,K2=1,then M=2;
K4=0,K3=0,K2=0,K1=1, then M=1;
K1
~
K4 all to be 0, then M=0
P01.20
Multiple step speed
Rotation direction
Bit0
~
15 corresponding to 0
~
15 phase
direction
0:forward direction 1:reverse direction
0
☆
P01.21
Multiple step speed
0/in-built plc 1
Lower limit frequency (P01.09)
~
maximum
frequency (P01.06)
0.00Hz
☆
P01.22
Multiple step speed
1/in-built plc 2
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆
P01.23
Multiple step speed
2/in-built plc 3
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆
P01.24
Multiple step speed
3/in-built plc 4
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆
P01.25
Multiple step speed
4/in-built plc 5
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆
P01.26
Multiple-step speed
5/in-built plc 6
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆
P01.27
Multiple step speed
6/in-built plc 7
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆
P01.28
Multiple step speed
7/in-built plc 8
Lower limit frequency(P01.09)
~
maximum
frequency(P01.06)
0.00Hz
☆