Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
31-
Functio
n code
Parameter name
Description
Default
Property
P01.08
Upper limit frequency
Lower limit frequency(P01.09)
~
maximum
frequency (P01.06)
50.00Hz
☆
P01.09
Lower limit frequency
0.00Hz
~
upper limit frequency
0.00Hz
☆
P01.10
Action when set
frequency lower than
lower limit frequency
0
:
Run at low limit frequency
1
:
Stop after delaying P01.11
2
:
Run at zero speed
0
★
P01.11
Delay time when set
frequency lower than
lower limit frequency
0.000s
~
30.000s
0.000s
★
P01.12
Jump frequency start up
protection
Unit/ten/hundred’digit
:
three jump frequency
1/2/3
0
:
Disable
1
:
Enable (avoid risk speed)
000
☆
P01.13
Jump frequency 1 lower
limit
0.00Hz
~
(P01.14)
0.00Hz
☆
P01.14
Jump frequency upper
limit
P01.13- (P01.06)Maximum frequency
0.00Hz
☆
P01.15
Jump frequency 2 lower
limit
0.00Hz
~
(P01.16)
0.00Hz
☆
P01.16
Jump frequency 2 upper
limit
P01.15
~
maximum frequency(P01.06)
0.00Hz
☆
P01.17
Jump frequency 3 lower
limit
0.00Hz
~
(P01.18)
0.00Hz
☆
P01.18
Jump frequency 3 upper
limit
P01.17
~
maximum frequency(P01.06)
0.00Hz
☆
Risk speed or Jump frequency start up protection is used to some situation which need avoid motor speed and
speed range,for example,due to mechanical resonance ,P01.12 will be enabled to avoide risk speed in forward or
reverse mode
。
Motor frequency
P01.18
P01.17
P01.16
P01.15
P01.14
P01.13
Giving frequency