Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
79-
P41.01
Sleep setting
value by
frequency
0.00Hz
~
600HZ,It will sleep if value is less
than this value
0.00Hz
☆
P41.02
Wake up
threshold by
frequency
0.00hz
~
600.00hz, ,It will wake up if value is
bigger than this value
0.00Hz
☆
When selecting frequency sleep and frequency wake-up, it must be set by P41.01 < P41.02. When the frequency
source is PID setting, and the frequency wake-up must be set to PID shutdown operation: P40.39 = 1.
P41.03
Sleep setting
value by
pressure
0
~
100.0%
0.0%
☆
P41.04
Wake up
threshold by
pressure
0.
~
100.0%
0.0%
☆
P41.05
Sleep delay time
0.0s
~
6000.0s
0.0s
☆
P41.06
Wake up delay
up
0.0s
~
6000.0s
0.0s
☆
P41.07
Sleep
decelerating
time
0.00(coast to stop)
~
60000s
Setting value decide by P03.16
P03.16 = 2, 0.00
~
600.00s;
P03.16 = 1, 0.0s
~
6000.0s;
P03.16 = 0, 0s
~
60000s
P41.07 set to 0,sleeping stop mode to free
coast
。
0.00s
☆
42 Group Simple PLC
r42.00
PLC current
running mode
Read only
-
●
r42.01
PLC current
running
remaining time
Read only
-
●
r42.02
PLC times of
cycles
Read only
-
●
P42.03
Simple PLC
running mode
Unit’digit:Running mode
0: Single cycle then stop
1: Single cycle then keep last speed
2: Recycle
3: Plc reset when single cycle stop
Ten’s digit:Saving selection at power off
0:Power off without saving 1:Power off with
saving
Hundred’digit:Power save selection at stop
0:Stop without power saving 1:stop with
saving
003
☆