ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 56
-
13 Group Motor 1 vector control
P13.00
Speed Proportional Gain
ASR_P1
0.1
~
100.0
12.0
☆
P13.01
Speed Integral Time
constant ASR_T1
0.001s
~
30.000s
0.100s
☆
P13.02
Speed Proportional Gain
ASR_P2
0.1
~
100.0
8.0
☆
P13.03
Speed Integral Time
constant ASR_T1
0.001s
~
30.000s
0.300s
☆
P13.04
ASR parameter Switching
frequency 1
0.00Hz
~
ASR switching frequency 2(P13.05)
5.00Hz
☆
P13.05
ASR parameter Switching
frequency 2
ASR switching frequency 1
~
600.00Hz(P13.04)
10.00Hz
☆
P13.00 and P13.01 are Speed adjuster parameter for low-speed use,scope of action from zero to P13.04
P13.02 and P13.03 are Speed adjuster parameter for high-speed use,scope of action from P13.05 to maximum
frequency
P13.04-P13.05 Two sets of parameter for linear tansitions
P13.06
Speed control torque limit
source selection
Unit’s digit
:
Electric torque limit source
0:digital setting
1:Ai1
2:Ai2
3-4(option card)
5:Pulse HDI
6:communication
Ten’unit
:
Electric torque limit source
Same as unit’digit
00
★
P13.07
Electric torque limit
0.0%
~
300.0%
160.0%
☆
P13.08
Upper limit of brake torque
0.0%
~
300.0%
160.0%
☆
P13.12
Torque current directives
filter time
Unit
:
current loop adjust cycle ,0
~
100
2
☆
P13.13
ACR Proportional Gain1
0.01
~
10.00
0.5
☆
P13.14
ACR Integral Time1
0.01
~
300.00ms
10.00ms
☆
P13.15
ACR Proportional Gain2
1
~
1000
0.5
☆
P13.16
ACR Integral Time2
0.01
~
300.00ms
10.00ms
☆
P13.17
Voltage feedforward Gain
0
~
100 improve the dynamic response of vector
control,
0
★
P13.19
Voltage margin
0.0%
~
50.0% improve the dynamic response of
weak magnetic curvature.
5.0%
☆
P13.20
Flux weakening adjuster
integral time
0.001s-5.000s
0.100s
☆
P13.22
Slip compensation
50%-200%
100%
☆
P13.23
SVC zero speed directives
0:no action 1:output DC current
0
★