Chapter 5 Function code
table
ICON500 high performance vector control frequency inverter user
manual
-
61-
P21.13
Digital keypad
personalized setting
Unit’s digit: quick editing function selection
0: invalid
1
:
Numeric frequency setting
2
:
Numeric torque setting
3
:
PID digital setting 0
Note: The quick editing function means that if the
current monitoring value is the output frequency
or command frequency under the monitoring
status, press the [ENTER] key to enter the
parameter editing interface directly. The edited
parameters are set by the ones digit of this
function code.
Ten’s digit: monitor pointer reset selection
0: When the display status is in the monitoring
status from other status, or when the running
monitoring status and stop monitoring status are
switched, the previously recorded monitoring
pointer position will be restored.
1: When the display status is in the monitoring
status by other status, or when the monitoring
status of running status and stop status are
switched, the monitor pointer will be reset to the
ones of P21.11 or P21.12.
Note: when power-on, the shutdown
monitoring pointer points to the P21.12 bits,
the operation monitoring pointer points to
P21.11 bits
01
★
P21.14
Load speed display factor
0.001
~
65.000
30.000
☆
P21.15
Load speed decimal point
digit
0
~
3
0
☆
r21.16
Load speed display
Load speed =P27.00*P21.10
Decimal point digit defined by P21.11
-
●
P21.17
Speed display unit
0
:
0.01Hz
;
1: 1Rpm
r10.12, r27.00, r27.01 displaying unit
selection
0
★