ICON500 high performance vector control frequency inverter user
manual
Chapter 5 function code
table
- 68
-
ten’unit:temperature detecting channel
0:AI3(IO card )
1:AI4(IO card)
P24.05
Motor 1 overheat
protection threshold
0.0
℃~
200.0
℃
120.0
℃
☆
P24.06
Motor 1 overheat warning
threshold
50%
~
100%
80%
☆
r24.07
Motor 1 temperature read
data
Unit 0.1
℃
-
●
P24.08
Motor 2 protection
option
Unit’digit:motor protection selectoin
0:no
1:overload protection(motor 2)
2:PTC1000
3:PTC100
Ten’unit: temperature detecting channel
0:AI3(IO Card)
1:AI4(IO Card )
01
☆
P24.09
Motor 2 overheat
protection threshold
0.0
℃~
200.0
℃
120.0
℃
☆
P24.10
Motor 2 overheat warning
threshold
50%
~
100%
80%
☆
r24.11
Motor 2 temperature read
data
Unit 0.1
℃
-
●
Motor can be protected from overload or overheat by setting P24.04 and P24.08 via motor1/2 protection
P24.12
Off load protection
0:effective 1:ineffective
0
☆
P24.13
Off load detection level
0.0%-100%
10.0%
☆
P24.14
Off load detection time
0.000s-60.000s
1.000s
☆