2.
Thread the battery connector through the battery cover. Position the battery cover in place and slide it
to the left to secure it.
3.
Connect the internal battery connector, as shown in Figure 335 on page 322. Each end of the keyed
connector has two wires: one red (+) and one black (−). Join the black wires and the red wires
together.
Note:
A small amount of arcing might occur when connecting the batteries. This is normal and does
not damage the unit or present any safety concerns.
4.
Push the front panel to the right to catch on the left end of the panel. Push the front panel forward
until the panel snaps into the right and middle sections of the 2145 UPS-1U, as shown in Figure 335
on page 322.
svc00070
Figure 333. Replacing the 2145 UPS-1U battery
svc00061
Figure 334. The 2145 UPS-1U internal-battery connector
Chapter 2. Removing and replacing parts
321
Summary of Contents for SAN Volume Controller 2145-CG8
Page 1: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Page 2: ......
Page 3: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Page 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 24: ...xxii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 30: ...xxviii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 54: ...24 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 362: ...332 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 364: ...334 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 371: ......
Page 372: ...Part Number 31P1584 Printed in USA GC27 2283 00 1P P N 31P1584...