Attention:
Check to make sure that the SAN Volume Controller that is powered by this 2145 UPS-1U is
shut down and turned off, prior to step 1. See MAP 5350 in the
IBM System Storage SAN Volume Controller
Troubleshooting Guide
.
1.
At the front of the 2145 UPS-1U, press and hold the on/off button (
1
in Figure 308) until the
power light is extinguished (approximately five seconds). On some versions of the 2145 UPS-1U, you
need a pointed device, such as a screwdriver, to press the on/off button. The 2145 UPS-1U enters
standby mode.
2.
At the back of the 2145 UPS-1U, remove the power cable retainer before disconnecting the SAN
Volume Controller power cable from load segment receptacle 2 (
3
in Figure 309).
3.
Disconnect the signal cable from the communication port (
2
in Figure 309).
4.
Disconnect the main power cable from the main power source (
1
in Figure 309).
Some SAN Volume Controller node types have two power supply units. Both power supplies must
be connected to the same 2145 UPS-1U. The SAN Volume Controller 2145-CF8 is an example of a
node that has two power supplies. The SAN Volume Controller 2145-8A4 is an example of a node
that has a single power supply.
5.
Remove the 2145 UPS-1U front panel, as shown in Figure 310 on page 308.
Note:
If you are having difficulty pulling the right side of the panel free from the 2145 UPS-1U,
insert a flat-blade screwdriver between the right side of the cover and the frame and gently pry it
free.
+ -
LOAD 1
LOAD 2
svc00003
1
Figure 308. The 2145 UPS-1U front-panel assembly
1yz09b
1
2
3
Figure 309. 2145 UPS-1U (rear view)
Chapter 2. Removing and replacing parts
307
Summary of Contents for SAN Volume Controller 2145-CG8
Page 1: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Page 2: ......
Page 3: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Page 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 24: ...xxii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 30: ...xxviii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 54: ...24 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 362: ...332 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 364: ...334 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 371: ......
Page 372: ...Part Number 31P1584 Printed in USA GC27 2283 00 1P P N 31P1584...