b.
For each dot of thermal grease, use two divisions on the syringe scale, which is 0.02 ml of grease.
You will use about half the syringe contents for the nine dots. Figure 298 shows how the
microprocessor appears with the nine dots of grease.
c.
Install the heat sink by gently squeezing it down onto the thermal grease and then tightening the
four retaining screws alternately and evenly.
7.
If this is a Rev 1 node, repeat steps 5 on page 295 and 6 on page 296 for the second microprocessor
and heat sink. If this is a Rev 2 node, continue with the next step.
8.
Replace either eight memory modules for the Rev 1 node or four memory modules for the Rev 2
node. See “Replacing the memory modules (DIMM)” on page 109.
9.
Replace the right air baffle, which is shown in Figure 299 on page 298.
a.
Locate the pin on the bottom of the air baffle in the locating hole on the system board.
b.
Push the baffle backwards to locate it in place.
svc00413
Figure 297. Estimating the position of the thermal grease dots
svc00414
Figure 298. Complete set of nine thermal grease dots on the microprocessor
Chapter 2. Removing and replacing parts
297
Summary of Contents for SAN Volume Controller 2145-CG8
Page 1: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Page 2: ......
Page 3: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Page 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 24: ...xxii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 30: ...xxviii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 54: ...24 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 362: ...332 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 364: ...334 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 371: ......
Page 372: ...Part Number 31P1584 Printed in USA GC27 2283 00 1P P N 31P1584...