Table 34. Dimensions
Maximum configuration
weight
Width
Depth
Height
The weight of the empty
rack is 244 kg (535 lb).
650 mm (25.5 in.)
1020 mm (40.0 in.)
1800 mm (71.0 in.)
Table 35. Temperature requirements
Operating
Nonoperating
10°C - 38°C (50°F - 100.4°F)
1°C - 60°C (33.8°F - 140°F )
Table 36. Environment requirements
Environment
Operating
Nonoperating
Noncondensing humidity
8% - 80%
8% - 80%
Wet bulb temperature
22.8°C (73°F)
22.8°C (73°F)
Maximum altitude
3048 m (10000 ft)
3048 m (10000 ft)
Noise emissions
Rack noise levels are a function of
the number and type of drawers
installed. See your server or
hardware specifications for specific
requirements
Rack noise levels are a function of
the number and type of drawers
installed. See your server or
hardware specifications for specific
requirements
Table 37. Service clearances
Front
Back
Sides
Top
762 mm (30 in. )
762 mm (30 in.)
762 mm (30 in.)
762 mm (30 in.)
Side and top clearances are optional during operation
Notes:
Figure 3. 0551 rack
20
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...