The rating of the HVDC PDU is 240 - 380 V dc, 90 A. The HVDC PDU has a permanently attached 4.3 m
(14 ft) power cord and is unterminated (no plug). The minimum cross-sectional area of the two
conductors and grounding conductor is 16 AWG (1.3 mm).
This PDU has six customer-usable Rong Feng RF-203P outlets that are rated at 240 - 380 V dc. Each outlet
is rated up to 10 A and is fed from one 20 A circuit breaker derated to 16 A. The HVDC PDU does not
have the nationally recognized test laboratory certification that is required for use in North America.
This PDU can be either vertically mounted in the rack side pockets or horizontally mounted by using
feature code (FC) EBA5 (mounting kit). If horizontally mounted, the PDU uses 1U of rack space.
Intelligent Switched PDU
Table 136. Intelligent Switched PDU features
Feature code (FC) Racks usage
Description
v
Voltage
v
Amperage
v
Phase
Provided power
receptacles
Supported power cords
(PDU to wall)
EPTG (PDU)
7014-T00 and
7014-T42 racks
v
200 - 240 V ac
v
Single phase or
three phase
1
v
16 A, 24 A, 32 A, 48
A, or 63 A
1
9 IEC 320-C19 and 3 IEC
320-C13 receptacles
“Supported PDU power
cords” on page 105
EPTJ (Field
Replaceable Unit
(FRU) kit)
EPTK (PDU)
7014-T00 and
7014-T42 racks
v
208 V ac
v
60 A
v
Three-phase
9 IEC 320-C19 and 3 IEC
320-C13 receptacles
Not applicable - fixed
IEC 60309, 60 A, plug
(3P+G) power cord
EPTL (FRU kit)
EPTM (PDU)
7014-T00 and
7014-T42 racks
v
200 - 240 V ac
v
Single phase or
three phase
1
v
16 A, 24 A, 32 A, 48
A, or 63 A
1
Twelve IEC 320-C13
receptacles
“Supported PDU power
cords” on page 105
EPTN (FRU kit)
EPTP (PDU)
7014-T00 and
7014-T42 racks
v
208 V ac
v
60 A
v
Three-phase
Twelve IEC 320-C13
receptacles
Not applicable - fixed
IEC 60309, 60 A, plug
(3P+G) power cord
EPTQ (FRU kit)
1
Amperage and phase depends on the power cord that is used. Three phase is wye wired. The voltage is 380 - 415 V
ac at the PDU input and 220 - 240 V ac at the PDU output.
Figure 53. HVDC PDU
116
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...