Table 80. Dimensions for rack (continued)
Width
Depth
Height
Weight (Empty)
EIA unit
capacity
Rack with
high-end
appearance front
door and rear
door
600 mm (23.6
in.)
1201 mm (47.3
in.)
2020 mm (79.5 in.)
181 kg (398 lb)
42 EIA units
Table 81. Weight capacity limits
Characteristics
Maximum weight
EIA unit capacity
Dynamic (rolling)
1134 kg (2500 lb)
18 kg (40 lb) / EIA average
Static
1678 kg (3700 lb)
32 kg (70 lb) / EIA average
Seismic certified
1170 (2580 lb)
20 kg (45 lb) / EIA maximum
Table 82. Dimensions for doors
Door model
Width
Height
Depth
Weight
Standard front
door and standard
back door
590 mm (23.2 in.)
1942 mm (76.5 in.)
31 mm (1.2 in.)
5.9 kg (13 lb)
Rear door heat
exchanger door
600 mm (23.6 in.)
1950 mm (76.8 in.)
129 mm (5.0 in.)
39 kg (85 lb) - empty
48 kg (105 lb) - filled
High-end
appearance front
door
590 mm (23.2 in.)
1942 mm (76.5 in.)
100 mm (3.9 in.)
9.1 kg (20 lb)
Table 83. Dimensions for side covers
Width
1
Depth
Height
Weight
2
12 mm (0.5 in.)
1070 mm (42.1 in.)
1942 mm (76.5 in.)
20 kg (44 lb)
1
Side covers increase the overall width of the rack by 12 mm (0.5 in.) per side, but are only used on the ends of the
rows.
2
Weight is for each side cover.
Table 84. Environment requirements
1
Environment
Recommended operating
Allowable operating
Nonoperating
ASHRAE class
A3
Airflow direction
Front-to-back
Temperature
2
18°C - 27°C (64°F - 80°F)
5°C - 40°C (41°F - 104°F)
1°C - 60°C (34°F - 140°F)
Humidity range
5.5°C (42°F) dew point (DP)
to 60% relative humidity
(RH) and 15°C (59°F) dew
point
-12.0°C (10.4°F) DP and 8%
- 80% RH
8% - 80% RH
Maximum dew point
24°C (75°F)
27°C (80°F)
Maximum operating
altitude
3050 m (10000 ft)
Shipping temperature
-40°C to 60°C (-40°F to
140°F)
62
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......