Table 51. Environment requirements (continued)
Environment
Operating
Nonoperating
Maximum altitude
3048 m (10 000 ft)
3048 m (10 000 ft)
Table 52. Noise emissions
Properties
Operating
Idle
L
WAd
(Category 2E, General business)
6.6 bels
6.3 bels
<L
pA
>
m
48 dB
46 dB
For a description of noise emission values, see Acoustics.
Table 53. Service clearances
Front
Back
Sides
Top
762 mm (30 in. )
762 mm (30 in. )
762 mm (30 in. )
762 mm (30 in. )
Side and top clearances are optional when operating.
Notes:
1.
The 1.8 meter rack has six EIA units of space remaining. This space will be filled with a three-EIA
filler panel and three of the one-EIA filler panels.
2.
Only the 4.3 m (14 ft) power cord features are offered for racked 9406-270 systems. There are a total of
four power cords that are routed through cable management arms. Also, there is a cable management
device that might be used to restrict the length of the power cord exiting the bottom of the rack. See
model 9406-270 Cable Poster Addendum included with the 0551 model 9406-270 rack.
3.
The rack does not have power distribution. Each model 9406-270 and 7104 requires a power cord of
sufficient length to reach the receptacle. The power cord feature codes for model 9406-270s must be
used to determine the appropriate receptacles.
Model 0554 and 7014-S11 rack
Hardware specifications provide detailed information for your rack, including dimensions, electrical,
power, temperature, environment, and service clearances.
Table 54. Dimensions
Dimension
Properties
Height
611 mm (24 in.)
Capacity
11 usable EIA units
Height with PDP - DC only
Not applicable
Width without side panels
Not applicable
Width with side panels
518 mm (20.4 in.)
Depth without doors
820 mm (32.3 in.)
Depth with front door
873 mm (34.4 in.)
Depth with sculptured style front door
Not applicable
Weight Base rack (empty)
36 kg (80 lb)
Weight Full rack
1
218 kg (481 lb)
Table 55. Electrical
Electrical characteristics
Properties
DC rack voltage (nominal)
Not applicable
30
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...