Note:
For optimum ventilation, it is recommended the rack or cabinet not have a front door. If the rack
or cabinet has doors, the doors must be fully perforated so that there is proper front-to-back airflow to
maintain the required drawer ambient inlet temperature as specified in the server specifications. The
perforations should yield at least 34 % minimum open area per square inch. Rear doors should not
create back pressure that can interfere with server fan operation.
General safety requirements for IBM products installed in a non-IBM rack or
cabinet
The general safety requirements for IBM products that are installed in non-IBM racks are:
v
Any product or component that plugs into either an IBM power distribution unit or mains power (via
a power cord), or uses any voltage over 42 V ac or 60 V dc (considered to be hazardous voltage) must
be Safety Certified by a Nationally Recognized Test Laboratory (NRTL) for the country in which it is
installed.
Some of the items that require safety certification might include: the rack or cabinet (if it contains
electrical components integral to the rack or cabinet), fan trays, power distribution unit, uninterruptible
power supplies, multi-outlet strips, or any other products that are installed in the rack or cabinet that
connect to hazardous voltage.
Examples of OSHA-approved NRTLs for the US:
– UL
– ETL
– CSA (with CSA NRTL or CSA US mark)
Examples of approved NRTLs for Canada:
– UL (Ulc mark)
– ETL (ETLc mark)
– CSA
The European Union requires a CE mark and a Manufacturer's Declaration of Conformity (DOC).
Certified products should have the NRTL logos or marks somewhere on the product or product label.
However, proof of certification must be made available to IBM upon request. Proof consists of such
items as copies of the NRTL license or certificate, a CB Certificate, a Letter of Authorization to apply
the NRTL mark, the first few pages of the NRTL certification report, Listing in an NRTL publication, or
a copy of the UL Yellow Card. Proof should contain the manufacturers name, product type, and model,
standard to which it was certified, the NRTL name or logo, the NRTL file number or license number,
and a list of any Conditions of Acceptance or Deviations. A Manufacturer's Declaration is not proof of
certification by an NRTL.
v
The rack or cabinet must meet all electrical and mechanical safety legal requirements for the country in
which it is installed. The rack or cabinet must be free of exposed hazards (such as voltages over 60 V
dc or 42 V ac, energy over 240 VA, sharp edges, mechanical pinch points, or hot surfaces).
v
There must be an accessible and unambiguous disconnect device for each product in the rack,
including any power distribution unit.
A disconnect device might consist of either the plug on the power cord (if the power cord is no longer
than 1.8 m (6 ft)), the appliance inlet receptacle (if the power cord is of a detachable type), or a power
on/off switch, or an Emergency Power Off switch on the rack, provided all power is removed from the
rack or product by the disconnect device.
If the rack or cabinet has electrical components (such as fan trays or lights), the rack must have an
accessible and unambiguous disconnect device.
v
The rack or cabinet, power distribution unit and multi-outlet strips, and products that are installed in
the rack or cabinet must all be properly grounded to the customer facility ground.
There must be no more than 0.1 Ohms between the ground pin of the power distribution unit or rack
plug and any touchable metal or conductive surface on the rack and on the products that are installed
in the rack. Grounding method must comply with applicable country's electric code (such as NEC or
Site and hardware planning
91
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...