Table 23. Electrical
1,2,3
(continued)
Electrical characteristics
Properties
Phase
Single
Notes:
1.
The power supplies for AC or DC voltage do not change. Only the power chunnel is different. The power
chunnel uses internal cables to carry power from the rear of the system node to the power supplies that are in
the front of the system node.
2.
All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
3.
AC and HVDC power supplies cannot be mixed in the same server or I/O drawer. IBM recommends that AC
products and HVDC products with HVDC PDUs are installed in separate racks. However, AC and HVDC
products can be supported in the same rack if all grounding (earthing) is done in accordance with the applicable
electrical code or codes. IBM provides documentation for different AC and HVDC products about the
disconnecting means for service. If a different disconnecting means is to be used for service of the equipment in
a rack with AC-powered and DC-powered products, the disconnecting means must be made clear to service.
Table 24. Environment requirements
Environment
Recommended operating
Allowable operating
Nonoperating
ASHRAE class
A3
Airflow direction
Front-to-back
Temperature
1
18°C - 27°C (64°F - 80°F)
5°C - 40°C (41°F - 104°F)
1°C - 60°C (34°F - 140°F)
Humidity range
5.5°C (42°F) dew point (DP)
to 60% relative humidity
(RH) and 15°C (59°F) dew
point
-12.0°C (10.4°F) DP and 8%
- 80% RH
5% - 80% RH
Maximum dew point
24°C (75°F)
27°C (80°F)
Maximum operating
altitude
3050 m (10000 ft)
Shipping temperature
-40°C to 60°C (-40°F to
140°F)
Shipping relative humidity
5% - 100%
1.
Derate maximum allowable dry-bulb temperature 1°C per 175 m above 950 m.
Table 25. Service clearances for rack-mounted expansion unit
Front
Back
Sides
914 mm (36 in.)
914 mm (36 in.)
914 mm (36 in.)
Side and top clearances are optional during operation.
Safety compliance:
This hardware is designed and certified to meet the following safety standards: UL
60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences.
5147-024, ESLL, and ESLS storage enclosures
Hardware specifications for 5147-024, ESLL, and ESLS storage enclosures provide detailed information for
your storage enclosures, including dimensions, electrical, power, temperature, environment, and service
clearances.
16
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...