Table 137. Intelligent Switched PDU specifications
Characteristics
Properties
Height
43.9 mm (1.73 in.)
Width
447 mm (17.6 in.)
Depth
350 mm (13.78 in.)
Additional clearance
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
Weight (not including power cord)
6.3 kg (13.8 lb)
Weight of power cord (approximate)
5.4 kg (11.8 lb)
Operating temperature at 0 - 914 m (0 - 3000 ft)
(room ambient)
10°C - 60°C (50°F - 140°F)
Operating temperature at 914 - 2133 m (3000 -
7000 ft) (room ambient)
10°C - 60°C (50°F - 140°F)
Operating humidity
8 - 80% (noncondensing)
Localized air temperature in PDU
60 °C (140 °F) maximum
Rated frequency (all feature codes)
50 - 60 Hz
Circuit breakers
Nine double-pole branch rated circuit breakers rated at 20 amps
for 1U C19 PDU models.
Six double-pole branch rated circuit breakers rated at 20 amps for
1U C13 PDU models.
The intelligent, switched AC power distribution unit (PDU) provides the capability to monitor the
amount of electrical power that is being used by devices that are plugged into the PDU. The PDU can
also cycle power to individual receptacles by using the switched function.
Table 138. EPTK/EPTL circuit breaker wiring
Circuit breaker number
IEC 320-C19 receptacle
IEC 320-C13 receptacle
1
1
1
2
2
3
3
4
4
4
5
5
6
6
7
7
7
8
8
9
9
Calculating the power load for 7188 or 9188 power distribution units
Learn how to calculate the power load for power distribution units.
Rack-mounted 7188 or 9188 power distribution unit
Learn about the power loading requirements and proper loading sequence for the 7188 or 9188 power
distribution unit.
Site and hardware planning
117
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...