Table 107. Noise emissions (Maximum configuration)
1
Acoustical characteristics
Idling
Operating
L
WAd
6.1 bels
6.1 bels
1.
The noise emission level that is stated is the declared (upper limit) sound power level, in bels, for a random
sample of servers. All measurements are made in accordance with ISO 7779 and reported in conformance with
ISO 9296.
7063-CR1 Hardware Management Console specifications
Hardware specifications for model 7063-CR1 provide detailed information for your Hardware
Management Console (HMC), including dimensions, electrical, power, temperature, environmental
specifications, and noise emissions.
The HMC controls managed systems, including the management of logical partitions and the use of
capacity on demand. Using service applications, the HMC communicates with managed systems to
detect, consolidate, and send information to IBM for analysis. The HMC provides service technicians with
diagnostic information for systems that can operate in a multiple-partitioned environment.
Use the following specifications to plan for your HMC.
Table 108. Dimensions
Width
Depth
Height
Weight
437 mm (17.2 in.)
705.3 mm (27.76 in.)
43.0 mm (1.7 in.)
14.5 kg (32 lb)
Table 109. Electrical
1, 2
Electrical characteristics
Properties
Maximum measured power
300 W
Maximum kVA
0.330
Maximum thermal output
1024 BTU/hr
Input voltage
100 - 127 V ac or 200 - 240 V ac
Frequency
50 or 60 Hz
1.
Preliminary data is subject to change.
2.
Power consumption and heat output vary depending on the number and type of optional features that are
installed and the power-management optional features that are in use.
Table 110. Environment requirements
Environment
Recommended operating
requirements
Allowable operating
requirements
Nonoperating
requirements
ASHRAE class
A2
Airflow direction
1
Front-to-back
Temperature
2
18°C - 27°C (64°F - 80°F)
10°C - 35°C (50°F - 95°F)
5°C - 45°C (41°F - 113°F)
Humidity range
5.5°C (42°F) dew point (DP)
to 60% relative humidity
(RH) and 15°C (59°F) dew
point
20% - 80% RH
8% - 80% RH
Maximum rate of change
5°C/20 hrs
Maximum dew point
21°C (70°F)
27°C (80°F)
Maximum operating
altitude
3050 m (10000 ft)
82
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...