N700 Operating Instructions and Parts Manual
9. Explanation of I-Group Function
89
9.2.2
Multi-speed operation function (CF1~CF4)
(1) Please set 2(CF1), 3(CF2), 4(CF3), 5(CF4) to Intelligent input terminals 1~8
(function code I001~I008).
(2) Multi-speed operation can be selected by binary operation (max.16 speeds) with 4 terminals.
(2
4
=16)
(3) Use A028-A042 to set frequency setting for speed-1 to speed-15.
(4) Set speed-0 with F001 when the method of frequency command is set as an operator.
Or when the method of frequency command is set as control terminal (Terminal), use O and
OI terminal.
Ex.) The setting method of Multi-speed operation in control terminals
- Setting by F011=1(Ter), I001=2(CF1), I002=3(CF2), I003=4(CF3), I004=5(CF4).
- Multi-speed1 ~ 15 is set with A028~A042.
Fig. 9- 9 Multi-speed operation function (CF1~CF4) in the control terminal
Signal Input for the terminal
Setting Frequency
Multi speed
CF4
CF3
CF2
CF1
Function Code Setting Value
0
speed
OFF OFF OFF OFF A027
0 Hz
1 speed
OFF
OFF
OFF
ON
A028
5 Hz
2 speed
OFF
OFF
ON
OFF
A029
10 Hz
3 speed
OFF
OFF
ON
ON
A030
20 Hz
4 speed
OFF
ON
OFF
OFF
A031
30 Hz
5
speed
OFF ON OFF ON A032
25 Hz
6 speed
OFF
ON
ON
OFF
A033
20 Hz
7 speed
OFF
ON
ON
ON
A034
15 Hz
8 speed
ON
OFF
OFF
OFF
A035
10 Hz
9 speed
ON
OFF
OFF
ON
A036
40 Hz
10
speed
ON OFF ON OFF A037
50 Hz
11 speed
ON
OFF
ON
ON
A038
60 Hz
12 speed
ON
ON
OFF
OFF
A039
45 Hz
13 speed
ON
ON
OFF
ON
A040
40 Hz
14 speed
ON
ON
ON
OFF
A041
35 Hz
15
speed
ON ON ON ON A042 30 Hz