N700 Operating Instructions and Parts Manual
10. Explanation of O-Group
113
10.2
Intelligent output terminal function
10.2.1
Signal during run(RUN)
(1) This function is to provide an output signal when the Inverter is in a running condition.
(2) Assign 0(RUN : signal during run) to an intelligent output terminal 11 -14 or the alarm relay
output terminal.
(3) The signal is still outputted when the dc braking operates.
(4) The timing chart is as follows.
Fig. 10- 7 Timing chart of RUN signal
Code value
Function name
Output state
Contents
OFF
The inverter is in the stop mode. (STOP Mode).
0
RUN
Signal during running
ON
The inverter is in the operation mode. (RUN Mode).
Table 10- 5 RUN signal during running
10.2.2
Frequency arrival signal 1~5 (FA 1 ~ FA 5)
(1) When the output frequency arrives at the setting frequency, an arrival signal is displayed.
(2) Assign 01 (FA1 : constant speed arrival signal), 02 (FA2 : over setting frequency), 06 (FA3 :
only setting frequency), 19 (FA4 : over setting frequency 2), 20 (FA5 : only setting frequency
2) to an intelligent output terminals 11-14.
Code
value
Function name
Output
state
Contents
OFF
When output frequency doesn't reach the frequency set in
F001.
1
FA1
Constant speed arrival
signal
ON
When output frequency reaches the frequency set in F001.
OFF
When output frequency reaches below the arrival frequency
during the deceleration which is set in o019.
2
FA2
Over setting frequency
arrival signal
ON
When output frequency reaches below the arrival frequency
during the acceleration which is set in o018.
OFF
When output frequency doesn't reach below the arrival
frequency during the acceleration which is set in o018 or the
arrival frequency during the deceleration which is set in o019.
6
FA3
Only setting frequency
arrival signal
ON
When output frequency reaches below the arrival frequency
during the acceleration which is set in o018 or the arrival
frequency during the deceleration which is set in o019.
OFF
When the output frequency reaches below Deceleration arrival
frequency in o021.
19
FA4
over setting frequency :
Arrival signal 2
ON
When the output frequency reaches over Deceleration arrival
frequency in o020.