N700 Operating Instructions and Parts Manual
7. Explanation of A-Group
68
7.13
Speed control setting (A090~A093)
(1) It is possible when the control mode(F012) setting is over 5.
(2) It is possible to set loop gain, loop constant, proportion gain and integral gain in the speed
control.
Code
Function name
Initial
value
Unit
Setting
range
Contents
A090
Speed control loop
gain
120 - 1~300
Lopp gain setting for the speed
controller
A091
Speed control loop
constant
60 - 1~120
Loop constant setting for the
speed controller
A092
Speed control
proportion gain setting
100 % 0~1000
Proportion gain setting for speed
controller
A093
Speed control integral
gain setting
100 % 0~1000
Integral gain setting for speed
controller
Table 7- 13 Speed control setting
(3) A090,
A092
:
If the frequency can’t reach the setting frequency in the acceleration / deceleration time
setting value, make a value of the A090 and A092 lager, and, if a vibration is occured, make a
value of the A090 and A092 lager.
(4) A091,A093
:
If an over-voltage or a speed over-shoot is occurred, make a value of the A091 and A093
smaller.
If you want to shot a deceleration time using the BRD, make a value of the A091 and A093
lager.
7.14
Load selection by speed control setting
Code
Function
name
Initial
value
Unit
Setting
range
Contents
0: Normal load (A090=120, A091=60, A092=100,
A093=100, Inertia=x1, L=initial value)
1: Lift load (A090=160, A091=100, A092=100,
A093=100, Inertia=x1, L=initial value)
2: Washing machine (A090=180, A091=20, A092=100,
A093=50, Inertia=x2.5, L=x0.9)
3: Press (A090=120, A091=60, A092=100,
A093=100, Inertia=x2, L=initial value)
A094
Load
Selction
by
speed
control
0 - 0~5
4~5: Reserved mode (A090=120, A091=30, A092=100,
A093=100, Inertia=x1, L=initial value)
Table 7- 14 Speed control setting for each loads