10.3.2
Analog output signals (AM/AMI) selection (o012~o017)
z
The AM terminal and the AM1 terminal can monitor
the output frequency or the output current.
z
The AM terminal has an analog output of 0-10V.
z
The AMI terminal has an analog output of 4-20mA.
(1) AM/AMI output signals selection
Select a signal to output from the following options.
Code
Function
name
Initial
value
Unit
Setting
range
Explanation
Full Scale Value
0
Fo : Output frequency
0~ Maximum frequency (Hz)
1
Io : Output current
0~200%
2
To : Output torque
0~200%
3
Vo : Output voltage
0~100%
4
Pin : Input electric power
0~200%
5
Load : Thermal load ratio
0~100%
o012
AM
Output
Selection
0 -
6
Flad : LAD frequency
0~ Maximum frequency (Hz)
0
Fo : Output frequency
0~ Maximum frequency (Hz)
1
Io : Output current
0~200%
2
To : Output torque
0~200%
3
Vo : Output voltage
0~100%
4
Pin : Input electric power
0~200%
5
Load : Thermal load ratio
0~100%
o015
AMI
Output
Selection
0 -
6
Flad : LAD frequency
0~ Maximum frequency (Hz)
Table 10- 19 AM/AMI output signals selection
Note) Display o012/o015=2(output torque) only at the time of SLV, SLV2, and V2
(2) AM/AMI
adjustment
This function is used to calibrate a meter connected to the AM and AM1 terminal.
Code
Function name
Initial value
Unit
Setting range
Contents
o013
AM offset
0.96
-
0.00~10.00
Offset setting
o014
AM adjustment
100.0
-
0.0~255.0
Gain setting.
o016
AMI offset
4.00
-
0.00~20.00
Offset setting
o017
AMI adjustment
100.0
-
0.0~255.0
Gain setting
Table 10- 20 AM/AMI adjustment
L
AMI
AM
0~10V analog voltage output
GND
4~20mA analog current output