(4) Set output current level at overload in overload advance notice level 1 (o026).
Code
Function name
Initial
value
Unit
Setting
range
Contents
o026
Overload advance
notice level 1
1.0 times
0.0~2.0
Inverter rated current
ⅹ
0. ~ 2.0 times
When reach overload advance notice
level 1 OL signal output
o027
Overload advance
notice level 2
1.0 times
0.0~2.0
Inverter rated current
ⅹ
0. ~ 2.0 times
When reach to overload advance notice
level 1 OL signal output
Table 10- 9 Overload advance notice level setting
Fig. 10- 11 Overload advance notice level setting
10.2.4
The Maximum PID Deviation Level (OD)
(1) It is possible to establish the maximum deviation level o029 on PID control. When the PID
deviation amount reaches the set level o029, it is possible to output OD(PID Max deviation) in
an intelligent output.
(2) o029 can be set from 0 to 100.0 % and corresponds with the command : from 0 to maximum
value.
Code
Function name
Initial
value
Unit
Setting
range
Contents
o029
PID deviation
setting level
3.0 % 0.0~100.0
Setting deviation range between the set
value and feedback value.
Table 10- 10 PID deviation setting level(o029)
(3) Assign 04 (OD) to intelligent output terminal 1~4 (o001~o004)
Code
value
Function name
Output
status
Contents
OFF
In case PID error is less than the setting value of deviation
signal
4
OD PID deviation
ON
In case PID error is more than the setting value of deviation
signal
Table 10- 11 OD PID deviation code value