N700 Operating Instructions and Parts Manual
9. Explanation of I-Group Function
106
9.3.3
O2-L terminal setting
(1) External analog input terminal O2 to L -10V can set output frequency in case input +10V
voltage.
Code
Function
Initial value
Unit
Setting range
Contents
I032
O2 input span calibration
Factory
setting
- 0~9999
Factory
setting
I033
O2 input zero calibration
Factory
setting
- 0~9999
Factory
setting
I034
O2 Start frequency
0.0
Hz
0.0 ~ 99.9
100~400.0
Start frequency setting
I035
O2 End frequency
0.0
Hz
0.0 ~ 99.9
100~400.0
End frequency setting
I036
O2 Start voltage
-100
%
0~100
Starting point for the voltage
input -10V
I037
O2 End voltage
100
%
0~100
Ending point for the voltage
input +10V
0 Singleness
1 Assistance,
irreversible
I038
O2 Start selection
0
-
2 Assistance
Table 9- 19 O2-L terminal setting
(2) -10V ~ ratio of +10V is as following.
(3) Setting O2 starts selection I038 by 0(singleness) O2, to use L signal individually, and AT
function does not allocate. (Please take care Intelligent input terminal function I002's initial
value was set by 16 (AT).)
(4) Or, I038 if input AT signal after set I049 by 1(O/O2) by 0/O2, L Simple cycle operation is
available.
(5) The frequency order method can be selectable according to O2 starts selection I038's setting
and AT terminal selection I049's association.
(6) For the detailed contents refer to 9.2.13 chapter(analog input voltage, electric current
switching).
(7) When an initial value 0 ~ the maximum frequency (F003) does not agree with the input
External electric current signal -10~10V, change correctly I032 and I033.
-10V ~ 0
:
-100~0%
0 ~ +10V
:
0~100%
ex)
When you input -5V ~ +5V to O2-L terminal,
please set I036 = -50%, I037= 50%.